Carrier 30GTN Service And Troubleshooting Manual page 32

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

KEYPAD
SUB-MODE
ENTRY
TEST
ENTER
OUTS
ENTER
COMP
ENTER
LEGEND
EXV — Electronic Expansion Valve
Table 8 — Service Test Mode and Sub-Mode Directory
ITEM
DISPLAY
ON/OFF
SERVICE TEST MODE
FR.A1
ON/OFF
FR.A2
ON/OFF
EXV.A
0-100%
FR.B1
ON/OFF
FR.B2
ON/OFF
EXV.B
0-100%
CLR.P
ON/OFF
COOLER PUMP RELAY
RMT.A
ON/OFF
REMOTE ALARM RELAY
CC.A1
ON/OFF
COMPRESSOR A1 RELAY
CC.A2
ON/OFF
COMPRESSOR A2 RELAY
CC.A3
ON/OFF
COMPRESSOR A3 RELAY
CC.A4
ON/OFF
COMPRESSOR A4 RELAY
UL.A1
ON/OFF
UNLOADER A1 RELAY
UL.A2
ON/OFF
UNLOADER A2 RELAY
HGBP
ON/OFF
HOT GAS BYPASS RELAY
CC.B1
ON/OFF
COMPRESSOR B1 RELAY
CC.B2
ON/OFF
COMPRESSOR B2 RELAY
CC.B3
ON/OFF
COMPRESSOR B3 RELAY
CC.B4
ON/OFF
COMPRESSOR B4 RELAY
UL.B1
ON/OFF
UNLOADER B1 RELAY
UL.B2
ON/OFF
UNLOADER B2 RELAY
ITEM EXPANSION
Use to Enable/Disable Manual Mode
FAN A1 RELAY
Fan 3 (040-050)
Fans 3,4 (060-110, 230B-315B)
Fans 1,2 (130 [60 Hz])
Fan 1 (130 [50 Hz], 150, 170, 230A- 270A,
Fans 1,11 (190-210, 290A, 315A,
FAN A2 RELAY
Fans 3,9 (130 [50 Hz], 150-210,
EXV % OPEN
FAN B1 RELAY
Fan 4 (040-050)
Fans 5,6 (060-090, 230B-245B)
Fans 5,6,7,8 (100,110, 255B-315B)
Fans 3,4,9,10 (130 [60 Hz])
Fan 2 (130 [50 Hz], 150, 170, 230A- 270A,
Fans 2,12 (190-210,290A,315A,
FAN B2 RELAY
Fans 4,10 (130 [50 Hz], 150-210, 230A-315A,
EXV % OPEN
32
COMMENT
330A/B, 360B [50 Hz])
360A, 360B [60 Hz], 390A/B-420A/B)
230A-315A, 330A/B-420A/B)
330A/B, 360B [50 Hz])
360A, 360B [60 Hz] ,390A/B-420A/B)
330A/B-420A/B)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents