Carrier 30GTN Service And Troubleshooting Manual page 37

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

Table 15 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
KEYPAD ENTRY
OPT2
ENTER
RSET
ENTER
SLCT
ENTER
ITEM
DISPLAY
CTRL
X
CCNA
XXX
CCNB
XXX
BAUD
X
LOAD
X
LOADING SEQUENCE SELECT
LLCS
X
LEAD/LAG CIRCUIT SELECT
LCWT
XX.X F
HIGH LCW ALERT LIMIT
DELY
XX
MIN MINUTES OFF TIME
CRST
X
COOLING RESET TYPE
CRT1
XXX.X °F
NO COOL RESET TEMP
CRT2
XXX.X °F
FULL COOL RESET TEMP
DGRC
XX.X F
DEGREES COOL RESET
DMDC
X
DEMAND LIMIT SELECT
DM20
XXX %
DEMAND LIMIT AT 20 MA
SHNM
XXX
LOADSHED GROUP NUMBER
SHDL
XXX %
LOADSHED DEMAND DELTA
SHTM
XXX MIN
MAXIMUM LOADSHED TIME
DLS1
XXX %
DEMAND LIMIT SWITCH 1
DLS2
XXX %
DEMAND LIMIT SWITCH 2
LLEN
ENBL/DSBL
LEAD/LAG CHILLER ENABLE
MSSL
SLVE/MAST
MASTER/SLAVE SELECT
SLVA
XXX
LLBL
ENBL/DSBL
LEAD/LAG BALANCE SELECT
LLBD
XXX HRS
LEAD/LAG BALANCE DELTA
LLDY
XX MIN
CLSP
X
COOLING SETPOINT SELECT
RL.S
ENBL/DSBL
CRMP
X.X
COOLING RAMP LOADING
Z.GN
X.X
DEADBAND MULTIPLIER
ITEM EXPANSION
CONTROL METHOD
CCN ADDRESS
CCN BUS NUMBER
CCN BAUD RATE
SLAVE ADDRESS
LAG START DELAY
RAMP LOAD SELECT
37
COMMENT
Default: 0
0 = Switch
1 = 7 Day Schedule
2 = Occupancy
3 = CCN Control
Default: 1
Range: 1 to 239
Default: 0
Range: 0 to 239
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
Default: 1
1 = Equal
2 = Staged
Default: 1 (size 080-420) 2 (size 040-070)
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 60
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Fluid
4 = Space Temperature
Default: 125 F
Range: 0 to 125 F
Default: 0° F
Range: 0 to 125 F
Default: 0° F
Range: −30 to 30 F
Default: 0
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
Range: 0 to 100%
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
Default: 60 minutes
Range: 0 to 120 minutes
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
Default: Disable
Default: Master
Default: 0
Range: 0 to 239
Default: Disable
Default: 168 hours
Range: 40 to 400 Hours
Default: 5 minutes
Range: 0 to 30 minutes
Default: 0
0 = Single
1 = Dual Switch
2 = Dual Clock
3 = 4 to 20 mA Input
Default: Enable
Default: 1.0
Range: 0.2 to 2.0
Default: 1.0
Range: 1.0 to 4.0