Carrier 30GTN Service And Troubleshooting Manual page 74

Air-cooled reciprocating with comfortlink controls 50/60 hz controls, start-up, operation, service, and troubleshooting
Table of Contents

Advertisement

CSM/FSM EQUIPMENT TABLE (Type 621H, Block 2)
LINE
1
2
3
4
5
6
7
8
9
WSM EQUIPMENT PART COOL SOURCE MAINTENANCE TABLE
DESCRIPTION
WSM Active?
Chilled water temp
Equipment status
Commanded state
CHW setpoint reset value
Current CHW setpoint
DESCRIPTION
Current Mode (1=Occup.)
Current Occup. Period #
Timed-Override in Effect
Time-Override Duration
Current Occupied Time
Current Unoccupied Time
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Previous Unoccupied Day
Previous Unoccupied Time
DESCRIPTION
Chiller Status
0 = Chiller is off
1 = Valid run state in CCN mode
2 = Recycle active
3 = Chiller is in Local Mode
4 = Power Fail Restart in Progress
5 = Shutdown due to fault
6 = Communication Failure
unused
Percent Total Capacity Running
Service Runtime
unused
unused
unused
Power Fail Auto Restart
Percent Available Capacity On
SUPERVISOR MAINTENANCE TABLE
STATUS
Yes
46.5 °F
On
Enable/Disable/None
2.0 ^F
44.0 °F
OCCUPANCY MAINTENANCE TABLE
OCCUPANCY SUPERVISORY
STATUS
0,1
0-8
Yes/No
0-4 hours
0:00
0:00
0:00
0:00
0:00
74
POINT
CHILSTAT
CAP T
HR MACH
ASTART
CAP A
POINT
WSMSTAT
CHWTEMP
CHLRST
CHLRENA
CHWRVAL
CHWSTPT
POINT
MODE
PER-NO
OVERLAST
OVR HRS
STRTTIME
ENDTIME
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM