Taking out of operation
10 Taking out of operation
DANGer
risk of death due to high DC and AC voltages!
f Wear insulating protective clothing and face protection.
f Inverters are only to be uninstalled by trained specialist personnel.
The trained specialist personnel must be granted permission by the
energy provider responsible.
f Switch off mains voltage supply (safety device).
f Set the switch knob of the DC disconnect to 0.
f Wait at least 40 minutes until the capacitors are discharged.
f Make sure that no voltage is applied to the DC cables.
WArNING
Injury may result if the inverter falls!
f Get a second person to help with assembly and disassembly.
f Wear safety shoes during assembly and disassembly.
f ensure that the inverter is positioned securely.
The procedure for taking inverters out of operation is the reverse of that
for installation and assembly.
58
Installation and user guide for inverter PLATINUM® 13000 TL, 16000 TL, 19000 TL, 22000 TL, 22001 TL