Installation
3.5.3 Connect DC voltage
DANGer
risk of death due to high DC voltage! A voltage is present at the PV
modules when it is bright.
f Before connecting the inverter, check whether voltage is applied to
the generator's DC voltage connection.
f Before connecting the inverter, check whether the polarity of the DC
voltage is correct.
f If voltage is applied, wear insulating protective clothing and face
protection.
f ensure that the cable plug has engaged completely with the socket.
f Detach the DC voltage cable only if the inverter is not in operation.
f Make sure that the DC disconnect a central isolation device can be
accessed freely.
f Do not earth the poles of the PV modules. The inverter does not have
a transformer.
WArNING
risk of electric shock and material damage!
f Use only the original DC voltage Multi-Contact MC4 cable plug.
f Only connect PV modules that meet the requirements of IeC 61730
class A.
f ensure that the max. DC voltage permitted is not exceeded.
f ensure that the max. direct current permitted per string is not
exceeded.
If more than one string is connected, make sure that the quantity and
type of solar modules and the voltage of strings to be connected in
parallel are the same.
The PLATINUM® TL inverters are equipped with 3 independently
operating MPP trackers with 3 terminal areas for the DC voltage.
The DC power levels may vary between connection areas, but should be
distributed as evenly as possible.
20