10 Taking out of operation

DANGER
Risk of death due to high DC and AC voltages!
f Wear insulating protective clothing and face protection.
f Inverters are only to be uninstalled by trained specialist personnel.
The trained specialist personnel must be granted permission by the
energy provider responsible.
f Switch off mains voltage supply (safety device).
f Set the switch knob of the DC isolator to 0.
f Wait at least 5 minutes until the capacitors are discharged.
f Make sure that no voltage is applied to the DC cables.
WARNING
Injury may result if the inverter falls!
f Get a second person to help with assembly and disassembly.
f Wear safety shoes during assembly and disassembly.
f Ensure that you have firm and secure footing.
The procedure for taking inverters out of operation is the reverse of that
for installation and assembly.
Installation and user guide PLATINUM Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
Taking out of operation