1.0 Appliance Type.

There are five build types within the ProCon HT & HTP range.
Please ensure you have the correct unit for the application and where required located
correctly within the cascade prior to beginning the installation.
1.1 Single Units.
(150 Product Code 96.30000-7182)
(225 Product Code 96.30000-7183)
The Single Unit is supplied with an integral low loss header.
This unit does not require the installation of a second low loss header remote from the
appliance.
The system's (Secondary) circulating pumps (Heating / HWS) are to be connected
(hydraulically) to the appliances flow and return connections.
The Single Unit is supplied complete with an integral RVS43 143 Single Unit Cascade
Manager wired to integral flow and return sensors.(QAZ36). An outside are sensor
(QAC34) is also supplied and located in the base of the unit.
Integral Low
Loss Header.
Complete with
Flow and Return
Sensors