Secti o n 5 ·
Insta ll ati on and S ta rt-U p

5.3 Electrical connection

General information
After the inverter has been installed in its fi xed location, the
electrical connection to the unit can be established.
The Powador may only be installed by trained and
authorised specialists.
You must adhere to all mandatory safety regulations, the
currently required technical connection specifi cations of the
responsible power supply company, as well as to other generally
applicable regulations.
WAR NIN G
Before you connect the inverter, disconnect the
AC and DC sides from all power sources and
secure them against being inadvertently switched
back on.
The connection of the PV generator and the grid connection
are established via PCB terminals in the inverter's connection
box (Powador 2002-3002, fi gure 5.4 and Powador 4202-6002,
fi gure 5.5).
A C T IO N
The door of the housing must be opened to do this. The
door is held shut with two Phillips recessed-head screws
on the right side of the housing.
NO T E
At the AC and DC connection terminals, the maximum con-
ductor cross-section that can be connected is 6 mm² (AC) or
10 mm² (DC). When wire sleeves are used, the cross-section
is reduced to 4  mm² (AC) or 6  mm² (DC). The strip-off
length is 12 mm (AC) or 15 mm (DC). A screwdriver (slotted,
3.5 mm) is to be used for the terminals in the inverter. Put
the screwdriver into the cut-out provided. Press the screw-
driver upwards slightly. Feed the cable into the spring termi-
nal. Put the screwdriver back into the original position.
Remove the screwdriver. The spring terminal is closed and
the cable is held in place.
Installation Instructions Powador 2002 / 3002 / 4202 / 5002 / 6002_EN
DA NGE R
DC
PV-
PV-
DC-
GFDI
DC+
PV+
PV+
2
1
1
2
connection
PV-
PV-
DC-
GFDI
DC+
PV+
PV+
3
3
(fi g. 5.7)
Figure 5.4: Overview of the Powador 2002-3002
DC
PE
PV-
PV-
DC- GFDI DC+ PV+
PV+
connection
2
1
1
2
PE
PV-
PV-
DC-
GFDI
DC+
PV+
PV+
3
3
(fi g. 5.8)
Figure 5.5: Overview of the Powador 4202-6002
AC
connection
(fi g. 5.6)
AC
connection
(fi g. 5.6)