Output Terminal Voltage - ONEAC SE041XAT User Instruction Manual

Se ii series parallelable ups user instruction manual
Table of Contents

Advertisement

Output Terminal
Voltage
ONEAC Sinergy SE II Series UPS User Manual
Table 5. 120/208/240 Output Terminal Voltage Configurations
X1
Terminal Voltage
(-)120
120 Volts (from X2 and X3 to
X5 and X6)
208 Volts (from X1 to X4)
240 Volts (from X1 to X6)
ATTENTION: *X2 & X3 are wired together, and X5 and X6 are wired together to provide full nameplate
rated current at 120 V (50 A for 6 kVA model and 83 A for 10 kVA model). However, each terminal can supply
only 1/2 of the total current and both terminals MUST be connected to the load in order to provide full power.
Table 6. 120/208/230/240 Output Terminal Voltage Configurations
X1
Terminal Voltage
0
ATTENTION: *X2 provides only 1/2 of nameplate rated current power (25 A for 6 kVA model and 40 A
for 10kVA model. User must provide over current protection (fuse or circuit breaker) of proper size
Table 7. 100/200 Output Terminal Voltage Configurations
X1
Terminal Voltage
(-)100
100 Volts (from X2 and X3 to
X5 and X6)
200 Volts (from X1 to X6)
ATTENTION: *X2 & X3 are wired together, and X5 and X6 are wired together to provide full nameplate
rated current at 100 V (50 A for 6 kVA model and 83 A for 10 kVA model). However, each terminal can supply
only 1/2 of the total current and both terminals MUST be connected to the load in order to provide full power.
X2
X3
E/G
X4
0
0
-
88
X2
X3
E/G
X4
120*
-
-
208
X2
X3
E/G
X4
0
0
-
-
Installation
X5
X6
(+)120* (+)120*
X5
X6
230
240
X5
X6
(+)100* (+)100*
.
13