ONePlus Series UPS
User Instruction Manual

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS.

Please read and save these instructions. This manual contains important
instructions for the ONePlus UPS. Follow these instructions during the
unpacking, installation and maintenance of the ONePlus UPS. If you have a
problem with the unit, please refer to this manual before calling ONEAC
Technical Services.
Licenses and Trademarks
ONEAC, Virtual Kelvin Ground and MopUPS are all registered trademarks and
ONePlus is a trademark of ONEAC Corporation. All other trademarks, product
and corporate names are the property of their respective owners.
ONEAC USA
27944 North Bradley Road
Libertyville, IL 60048-9700
USA
Telephone: (847) 816-6000
Toll Free: (800) 327-8801
Facsimile: (847) 680-5124
Entire contents copyright © 2004 ONEAC Corporation. All rights reserved. Reproduction in whole or
in part without permission is prohibited. All information subject to change without notice.
913-577 Rev. -
ONePlus UPS User Instruction Manual
ONePlus UPS
ONEAC EUROPE
George Curl Way
Southampton, Hampshire SO18 2RY
United Kingdom
Telephone: +44 (0) 2380 610311
Facsimile: +44 (0) 2380 612039
12/04

Advertisement

Table of Contents
loading

Summary of Contents for ONEAC ONePlus Series

  • Page 1: Important Safety Instructions

    Toll Free: (800) 327-8801 Facsimile: +44 (0) 2380 612039 Facsimile: (847) 680-5124 Entire contents copyright © 2004 ONEAC Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited. All information subject to change without notice. 913-577 Rev. -...
  • Page 2: Table Of Contents

    Introduction ..................1 Registering Your ONEAC UPS ............. 1 Technical Support ................1 FCC Compliance ................2 Safety (English) ................... 3 Sicherheitshinweise (Deutsch) ............. 4 Mesures de sécurité (Français) ............5 Seguridad (Español) ................6 Theory of Operation ................7 AC Power Mode ................
  • Page 3: Introduction

    We take pride in every unit that leaves our manufacturing facility. Registering Your To ensure that your ONePlus Series UPS model and serial number are registered, complete and mail the ONEAC UPS enclosed postage-paid warranty card or go on line at www.oneac.com.
  • Page 4: Fcc Compliance

    FCC Compliance ATTENTION: Changes or modifications to this unit not expressly approved by the party responsible or in Compliance FCC compliance could void the user’s authority to operate the equipment. This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules.
  • Page 5: Safety (English)

    Safety Safety (English) WARNING: This equipment services power from more than one source. The output receptacles may have voltage even when the unit is unplugged. UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode. Unplugging the UPS does not remove the electrical charge.
  • Page 6: Sicherheitshinweise (Deutsch)

    Sicherheitshinweise Sicherheitshinweise (Deutsch) ACHTUNG: Dieses Gerät erhält seinen Strom von mehr als einer Quelle. Die Ausgangssteckdosen führen unter Umständen Spannung, selbst wenn der Stecker des Gerätes ausgesteckt wurde. Für USVs müssen andere Sicherheitsmaßnahmen als für die meisten Elektrogeräte ergriffen werden, da die USV durch Ausstecken in den Reservebetrieb gebracht wird.
  • Page 7: Mesures De Sécurité (Français)

    Mesures de sécurité Mesures de sécurité (Français) AVERTISSEMENT : Cet équipement est alimenté par plus d'une source. Des tensions peuvent être présentes aux prises de sortie, même lorsque l'unité est débranchée. Le problème de sécurité sur l'UPS diffère de celui de la plupart des équipements électriques, car lorsqu'il est débranché, il se met en mode de réserve.
  • Page 8: Seguridad (Español)

    Seguridad Seguridad (Español) ADVERTENCIA: Este equipo suministra alimentación desde más de una fuente. Los tomacorrientes de salida pueden tener voltaje aun cuando la unidad esté desenchufada. Las UPS (fuentes de alimentación ininterrumpibles) cuentan con una característica de seguridad diferente a la mayoría de los equipos eléctricos, ya que al desenchufarse, quedan en el modo de reserva.
  • Page 9: Theory Of Operation

    Theory of Operation Theory of The ONePlus UPS has two operating modes: Conditioned AC Power and Conditioned Battery Operation Backup. AC Power Mode When utility AC power is present and within the correct voltage range, the UPS provides fully conditioned power: •...
  • Page 10: Output Overload Protection

    Theory of Operation If the battery becomes exhausted while maintaining the load, battery backup terminates and the UPS output turns off. A low battery warning is sounded and transmitted via the communications port approximately two minutes prior to termination of battery backup.
  • Page 11: Setup And Installation

    Setup and Installation • If the circuit breaker trips with nothing plugged into the output receptacles, there may be an internal problem with the UPS. Call ONEAC Technical Services for assistance (refer to page 1). Setup and Before shipment, this product was tested, inspected...
  • Page 12: Ventilation

    Setup and Installation To keep the battery enclosure fully charged and to maximize the life of the battery, plug the UPS into an outlet while it is in storage. If the UPS is stored without power access, plug it into a power source for 24 hours at least once every 4 - 6 months.
  • Page 13: Connections

    Setup and Installation Connections Before beginning, shut down and unplug the equipment to be protected. DO NOT make any connections or attempt to use any of the equipment until all the following connection instructions have been reviewed and completed. Site Wiring Fault Indicator USB Communication Port Serial Communication Port Input Circuit Breaker...
  • Page 14: Oneplus Front Panel

    Setup and Installation 1. Plug the ONePlus UPS into a properly wired AC electrical outlet. 2. Plug the equipment to be protected into the UPS. CAUTION: Do not attach laser printers to the UPS. A laser printer periodically draws significantly more power during use and may overload the UPS.
  • Page 15: Power Switch

    Setup and Installation and indicators, see System Code Status Chart on page 27. Power Switch Audible Alarm/Load Power Battery Fault Temperature 250-400 VA ONePlus UPS Front Panel Power Power Switch Battery Fault Audible Alarm/Load Temperature 600-1000 VA ONePlus1 fig. 5: ONePlus UPS Front Panel Power Switch With the UPS connected to a properly wired AC input power source, press the power switch (...
  • Page 16: Self-Test

    Setup and Installation Self-Test The UPS performs a self-test when it is first plugged in and turned ON. A green LED indicates normal AC output. The three LEDs on the front panel will indicate the status. A blinking yellow LED shows the battery is being charged.
  • Page 17 Setup and Installation Overload If the load on the UPS exceeds its capacity, the red and green LEDs will blink. The audible alarm will sound once every minute. If the UPS is heavily overloaded, the audible alarm will sound continuously and will shut down in 4 seconds.
  • Page 18: Communications

    Setup and Installation The front panel indicator lights serve four functions: 1. To indicate status of the UPS, whether operating normally or in fault condition. See System Code Status Chart on page 27 for details. 2. To indicate % of load connected to the UPS. To determine % load, the UPS must be on AC power, not on battery.
  • Page 19 1. Connect the computer to the UPS communications port using the supplied USB communications cable. NOTE: If a serial connection is required, contact the factory to purchase optional serial cable (ONEAC part number CA-2B10S-03). NOTE: RS232 and USB communications ports cannot be used simultaneously.
  • Page 20 Setup and Installation Table 1. Pin Signals for Supplied USB Cable PIN # Signal Name Function Position Low battery simulated contact; 20 mA, 30 VDC contact rating Low batt Closes when low Receive from external device and shut down input Transmit to external device —...
  • Page 21: Features And Specifications

    Features and Specifications Features and Your ONEAC ONePlus UPS features full output isolation and power conditioning with Virtual Kelvin Specifications ® Ground output filtering. This provides the highest level of protection from power line disturbances available. ONEAC’s ONE is a standard feature on all GROUND ONePlus UPSs.The patented technology diverts...
  • Page 22: Physical And Electrical Specifications

    Features and Specifications Physical and Surge voltage withstand capability: ANSI/IEEE Electrical C62.41 Category A&B, 6 kV/ 200 & 500 Amp, 100 kHz ringwave Specifications Surge voltage let-through (max): Less than 10 V Normal mode (L-N), less than 0.5V Common mode (N-G) when subjected to 6 kV ANSI/IEEE C62.41 Cat.
  • Page 23: Specifications And Characteristics

    Features and Specifications Specifications and Characteristics Table 2. Physical/Electrical Specifications and Performance Characteristics Specification and Characteristics ONePlus250 ONePlus400 ONePlus600 ONePlus1000 Part Number ONE254AG-SE ONE404AG-SE ONE604AG-SE ONE1004AG-SE Maximum Load VA/W 250/167 400/268 600/402 1000/670 Rated Power Factor UPS .67 Crest Factor <3 Nominal Input Voltage 120 VAC...
  • Page 24 Features and Specifications Table 2. Physical/Electrical Specifications and Performance Characteristics Specification and Characteristics ONePlus250 ONePlus400 ONePlus600 ONePlus1000 Operating Elevation 0 to 3,000 m (0 to 10,000 ft.) Storage Elevation 0 to 15,000 m (0 to 50,000 ft.) UPS Dimensions(HxWxL) in. 7.1 x 5.5x 13.8 7.1 x 5.5x 15.4 9.3 x 7.1 x 15.0 9.3 x 7.1 x 15.0...
  • Page 25: Typical Runtimes

    5 min. NOTE: Due to application specific conditions, your actual run time may be different. Battery NOTE:To obtain new batteries, contact ONEAC Technical Services at (847) 816-6000, option 3 or Considerations toll free at (800)-327-8801, option 3. In Europe, dial +44 (0) 1235 534721.
  • Page 26: Battery Replacement Procedures

    Battery Considerations • Do not lay tools or metal parts on the battery. WARNING:DO NOT attempt to change battery wiring or connectors. Doing so can cause injury. WARNING:Replace batteries with the same type and quantity as previously installed in the unit. WARNING:DO NOT disconnect the batteries if the UPS is in battery mode.
  • Page 27: Testing New Batteries

    8. Carefully snap plastic bezel into the closed position. 9. Dispose of the old battery pack according to current environmental regulations. See Battery Disposal, below, if you would like ONEAC to dispose of depleted battery. Testing New NOTE:Once new batteries are installed it is...
  • Page 28: Battery Disposal

    534721 for an RMA number. Mark the RMA number on the packing slip and shipping carton. 2. Phone ONEAC Corporation for the number of a local battery collection site (US only). 3. Make arrangements with a local auto shop that collects automotive batteries for reprocessing.
  • Page 29: Troubleshooting

    You can access these numbers on the back panel of the unit on a label located near the receptacles. Always check with ONEAC Technical Services before attempting to repair or return any ONEAC product. Table 4. System Code Status Chart Unit Status...
  • Page 30 Unit not plugged in. Plug unit into wall outlet. No batteries installed or Check for batteries or contact ONEAC defective batteries. Technical Services for replacement. Reduce the load on the UPS by UPS’s input circuit unplugging the load and press the breaker tripped.
  • Page 31 Troubleshooting Table 5. Troubleshooting Problem Possible Cause Solution If yellow LED is blinking, • Check battery connection or there is no battery • replace battery. connected or detected. Fault LED is blinking If green LED is blinking Reduce load on the UPS (disconnect or off, the output is one ore more devices) and restart the overloaded.
  • Page 32: Warranty

    This warranty is limited to repairing or replacing, at ONEAC’s option, any defective component, circuit board, or module contained within the product only when it is returned with an ONEAC Return Material Authorization (RMA) number to ONEAC or to an ONEAC-designated repair facility. In all cases, the...