ONEAC Sinergy Series Important Safety Instructions Manual

Advertisement

Sinergy™ Series User Instruction Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
Please read and save these instructions. This manual contains important instructions for ONEAC models:
• S700A
• S1000XA
• S2000XA
• S3000XA
• SBP1000
• SBP3000
Follow these instructions during installation and maintenance of the UPS and batteries.
If you have a problem with the UPS, please refer to this manual before calling the Technical Support
Department. The Troubleshooting section on page 28 addresses most UPS-related issues.
FCC Compliance
ATTENTION: Changes or modifications to this unit not expressly approved by the party responsible or in FCC
compliance could void the user's authority to operate the equipment.
This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial
environment. The UPS generates, uses, and can radiate radio frequency energy. If installation and use is not in accordance
with the instruction manual, it may cause harmful interference to radio communications.
ATTENTION: Operation of this equipment in a residential area may cause harmful radio communications
interference. The user is responsible for correcting the interference.
ONEAC USA
27944 North Bradley Road
Libertyville, IL 60048-9700
USA
Telephone: (847) 816-6000
Toll Free: (800) 327-8801
Facsimile: (847) 680-5124
913-459 Rev. D1
ONEAC Sinergy UPS User Manual
• S700A-RM
• S1000XA-RM
• S2000XA-RM
• S3000XA-RM
• SBP1000-RM
• SBP3000-RM
• SE61XA (SE41XA)
• SE101XA (SE81XA)
• SE203XA (SE153XA)
• SBPE61
• SBPE101
ONEAC EUROPE
George Curl Way
Southampton, Hampshire SO18 2RY
United Kingdom
Telephone: +44 (0) 2380 610311
Facsimile: +44 (0) 2380 612039
i

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sinergy Series and is the answer not in the manual?

Questions and answers

Summary of Contents for ONEAC Sinergy Series

  • Page 1 Sinergy™ Series User Instruction Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Please read and save these instructions. This manual contains important instructions for ONEAC models: • S700A-RM • SE61XA (SE41XA) • S700A • S1000XA • S1000XA-RM • SE101XA (SE81XA) • S2000XA-RM •...
  • Page 2: Table Of Contents

    Registering your ONEAC UPS ........
  • Page 3: Chapter 1 Introduction

    1.1 Registering your ONEAC UPS To ensure that your Sinergy Series model and serial number are registered, complete and mail the enclosed postage-paid warranty card or go online at www.oneac.com. 1.2 Technical Support and Service ONEAC offers 24-hour technical support.
  • Page 4: Warning For Se61, Se101 And Se203

    • In emergencies (e.g. damaged case, controls or power cables, penetration of liquids or foreign matter) put the device into BYPASS, disconnect the power plug and contact ONEAC Technical Services at 1-800-327-8801 Opt. 3 or 1-847-816-6000. The special conditions for installing the hardwired devices, SE61, SE101 and SE203 are in chapter 4, “Installation and Commissioning”...
  • Page 5: Chapter 2 Display And Operation Elements

    95 - 100% ® The most reliable method for determining actual battery runtime is the application of ONEAC MopUPS software. With this software, the prospective remaining battery capacity is indicated before and during an AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application...
  • Page 6: Front

    Operating the switch | activates the inverter. After a delay of approximately 5 seconds the BYPASS indicator extinguishes and the INVERTER indicator illuminates. NOTE: To switch from BYPASS to INVERTER, press the | switch for at least 1 second. (A tone sounds confirming the switch). ONEAC Sinergy UPS User Manual...
  • Page 7: Rear

    Input fuse when the device is switched off and unplugged. Mains (input) connection Output receptacles Fig. 2: S1000 Rear View * Call ONEAC Technical Services for information on setting output voltages (1-800-327-8801, opt. 3 or +1-847-816-6000). ONEAC Sinergy UPS User Manual...
  • Page 8 Connection for additional batteries Fans Output Receptacle Circuit Breakers Input circuit breaker Output receptacles Linecord Fig. 4: S3000 Rear View * Call ONEAC Technical Services for information on setting output voltages (1-800-327-8801, opt. 3 or +1-847-816-6000) ONEAC Sinergy UPS User Manual...
  • Page 9 (SE101 with optional PDU shown) Output circuit breaker Input circuit breaker Mains fuse and Battery switch Optional PDU Fig. 6: SE81 or SE101 * Call ONEAC Technical Services for information on setting output voltages (1-800-327-8801, opt. 3 or +1-847-816-6000) ONEAC Sinergy UPS User Manual...
  • Page 10 Fans Output circuit breaker Input circuit breaker Maintenance bypass switch Wiring box cover (or optional PDU) Fig. 7: SE203 * Call ONEAC Technical Services for information on setting output voltages (1-800-327-8801, opt. 3 or +1-847-816-6000) ONEAC Sinergy UPS User Manual...
  • Page 11: Chapter 3 Rackmount Series

    3.2.1 Selection of the mounting location The Sinergy Series Rackmount units are designed to be mounted in a 19-inch rack. When installing the UPS, please consider the heavy weight of some components. Preferably, they should be installed in the lower section of the rack.
  • Page 12 NOTE: Before connecting a battery pack to the UPS, the miniature circuit breaker of the battery pack must be switched to “OFF.” After electrical connection with the UPS, this breaker has to be switched “ON.” NOTE: The S2000-RM and S3000-RM have no internal batteries. ONEAC Sinergy UPS User Manual...
  • Page 13: Unit Rear View And Connections

    NOTE: No battery extension can be connected to the 700 VA unit. Fig. 9: S700-RM Fig. 10: S1000-RM Fig. 11: Battery Pack - SBP1000-RM To connect the battery pack to the unit, use the separate cable supplied. ONEAC Sinergy UPS User Manual...
  • Page 14 UPS, each further extension is connected by means of the two cables. Each cable is non-interchangeable, because the sockets are coded. Fig. 12: S2000-RM Fig. 13: Battery Pack - SBP3000-RM 3.3.3 S3000-RM Fig. 14: S3000-RM Fig. 15: SBP3000-RM ONEAC Sinergy UPS User Manual...
  • Page 15: Chapter 4 Installation And Commissioning

    L1/N and L2 (for SE61 and SE101) or L1, L2, and L3 (for SE203). See Table 2, “Minimum Requirements for Sinergy Series UPS Installation,” on page 15 for minimum wire gauge, wire temperature and screw torque requirements.
  • Page 16 User must properly fuse these outputs to this rating. 9. Connect the UPS to the battery cabinet(s) (if required) See Table 2, “Minimum Requirements for Sinergy Series UPS Installation,” on page 15 for minimum wire gage, wire temperature and screw torque requirements.
  • Page 17 Table 2. Minimum Requirements for Sinergy Series UPS Installation SE61 (SE41) SE101 (SE81) SE203 (SE153) Min. Min. Min. Min. Min. Min. Term ID Description Term Term Term Wire Wire Wire Wire Wire Wire Torque Torque Torque Gauge Temp. Gauge Temp.
  • Page 18: Commissioning Of The S Series

    3. When the signal interface is used, then the connection cable (accessories) is linked between UPS and computer system. Please see instructions in the documentation for the accessories. 4. Switch on the loads. 5. Switch on the UPS by operating the switch | on the front panel. ONEAC Sinergy UPS User Manual...
  • Page 19: Commissioning Of The Se Series

    UPS. If only one device is connected to the UPS, then its energy demand exceeds the nominal rating of the UPS, which means that a UPS with a higher power rating has to be used. An overload alarm signal (1 signal per second) is heard. ONEAC Sinergy UPS User Manual...
  • Page 20: Commissioning Of An External Battery Cabinet

    The UPS is now ready for operation. NOTE: Battery charging times may be longer when using an external battery cabinet. WARNING: Battery Plug 1 Circuit Breaker Battery Plug 2 Fig. 20: Connection of Battery Extensions for devices S1000 ONEAC Sinergy UPS User Manual...
  • Page 21 Battery Plug for Connection of an Additional Battery Extension Fig. 21: Connection of an External Battery Cabinet to Type SE61 Hardwire Type of connection not yet defined Fig. 22: Connection of an External Battery Cabinet to TypeSE101 ONEAC Sinergy UPS User Manual...
  • Page 22 Table 4. Technical data of the connection cable SE101 SE203 Minimum permissible cable cross section 20 mm , 4 AWG 4 AWG Maximum permissible cable cross section 20 mm , 4 AWG 4 AWG Nominal operating voltage 240 VDC 240 VDC ONEAC Sinergy UPS User Manual...
  • Page 23: Chapter 5 Operational Characteristics

    Thereafter the elements are on according to the UPS load status. • The “BYPASS” indicator turns off after approximately 5 seconds and the “Inverter” indicator illuminates. The load is supplied through the inverter, the energy is taken from the mains. ONEAC Sinergy UPS User Manual...
  • Page 24: Modes Of Operation

    In the event of a mains failure, the inverter continues to supply the loads uninterruptedly, the energy is taken from the battery. In this operation mode, an acoustical signal is given in intervals of approximately 4 seconds. When reaching the battery’s energy minimum, this signal is given every second. ONEAC Sinergy UPS User Manual...
  • Page 25 In the event of large overload (> 140%) switch-over to bypass is initiated and the inverter is blocked. The energy is taken from the mains. This is not a normal operating status. In the event of mains failure the loads will no longer be supplied (no UPS operation). ONEAC Sinergy UPS User Manual...
  • Page 26: Chapter 6 Description Of The Interface

    The RS232 signal RXD can also be used as input signal, when the sequential interface is not used. The 5 alarm outputs are open-collector outputs. Fig. 27: COM A signal Definition and Connection The interface COM A is galvanically separated from all other circuits. ONEAC Sinergy UPS User Manual...
  • Page 27: Optional Interface Com B

    In the following the function of the interface signals for version COM B is described. The optional interface COM B provides potential-free signalling contacts and a shutdown input and an insulated auxiliary supply. Fig. 28: Simplified Schematic of Interface Connections ONEAC Sinergy UPS User Manual...
  • Page 28: Emergency Power Off (Epo) (Model Se203X Only)

    17 must be followed. The EPO circuit may be extended by connecting normally closed switches in series between the EPO connector pins. Activating (opening) any of the series switches will cause the UPS to shut off its output. ONEAC Sinergy UPS User Manual...
  • Page 29: Chapter 7 Maintenance

    Do not allow liquid to get inside the UPS. Make sure that the air vents on the UPS are not obstructed. Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth. ONEAC Sinergy UPS User Manual...
  • Page 30: Chapter 8 Troubleshooting

    If problem persists, reached the end of its useful life. then call Technical Services. Charging device is faulty. OVERLOAD LED indicator is on. Overload at the UPS output. Reduce load to the permissible value. ONEAC Sinergy UPS User Manual...
  • Page 31: Chapter 9 Technical Support

    NOTE: All calls received before 7 a.m. or after 7p.m. Central Standard Time are forwarded to a cell phone. An ONEAC Technical Support Representative will return your call within one half hour between 5 p.m. and 10 p.m. Central Standard Time. Except for emergencies, calls received between 10 p.m. and 7 a.m. will be returned during normal business hours.
  • Page 32: Chapter 10 Specifications

    Chapter 10 Specifications Table 7. ONEAC Sinergy UPS (S Series) North America UPS Model S700A S1000XA S2000XA S3000XA Electrical Data Rating 700 VA 1 kVA 2 kVA 3 kVA Input Voltage 120 VAC single-phase Voltage range A 80 - 138 VAC Frequency 50/60Hz ±...
  • Page 33 Table 7. ONEAC Sinergy UPS (S Series) North America UPS Model S700A S1000XA S2000XA S3000XA Common Data Electrical safety UL1778 Radio interference level FCC Part 15 Class A IEC 801-2,level 4 / IEC 801-3,level 3; Interference immunity IEC 801-4,level 4 / IEC 801-5,level 2) Efficiency...
  • Page 34 Table 7. ONEAC Sinergy UPS (S Series) North America UPS Model S700A S1000XA S2000XA S3000XA Connections Mains connections Type 5-15P 5-15P L5-20P L5-30P Fusing mains / CB 10 A 15 A 20 A 30 A Load connection Quantity Type 5-15R...
  • Page 35 Table 8. ONEAC Sinergy UPS (S Series) (International) UPS Model S700I S1000XI S2000XI S3000XI Runtime (min.), 2 batteries 140/60 215/92 140/57 half load/full load Output Voltage 208, 220, 230, 240 VAC Voltage tolerance ±3% Frequency with mains control see input frequency Frequency with internal control 50/60 Hz, ±...
  • Page 36 Table 8. ONEAC Sinergy UPS (S Series) (International) UPS Model S700I S1000XI S2000XI S3000XI Mechanical Data Weight - lbs. (kg) 28.6 (13) 35.3 (16) 75 (34) 75 (34) Dimensions - HxWxD in. (mm) 8.9 x 5.7 x 16 (225 x 145 x 405) 13.8 x 7.9 x 18.5 (350 x 200 x 470)
  • Page 37 36 V 96 V 96 V Net weight (kg) — 47.5 (21.5) 59.5 (27) 59.5 (27) Dimensions — same as UPS NOTE: for electrical specifications see “ONEAC Sinergy UPS (S Series) North America” on page 30. ONEAC Sinergy UPS User Manual...
  • Page 38 36 V 96 V 96 V Net weight (kg) — 47.5 (21.5) 59.5 (27) 59.5 (27) Dimensions — same as UPS NOTE: for electrical specifications see “ONEAC Sinergy UPS (S Series) (International)” on page 32. ONEAC Sinergy UPS User Manual...
  • Page 39 Table 12. S2000-RM-1 Runtimes in Minutes S2000-RM S2000-RM S2000-RM S2000-RM S2000-RM Watt + 1 BP + 2 BP + 3 BP + 4 BP + 5 BP 1000 1250 1500 1050 1750 1225 2000 1400 ONEAC Sinergy UPS User Manual...
  • Page 40 S3000-RM S3000-RM S3000-RM Watt + 1 BP + 2 BP + 3 BP + 4 BP + 5 BP 1000 1250 1500 1050 1750 1225 2000 1400 2250 1575 2500 1750 2750 1925 3000 2100 ONEAC Sinergy UPS User Manual...
  • Page 41 Table 14. ONEAC Sinergy UPS (SE Series) North America SE61XA SE101XA SE203XA UPS Model (SE41XA*) (SE81*) (SE153XA*) * Models may be upgraded to base kVA of UPS shown. Electrical Data Rating 6 kVA 10 kVA 20 kVA Input Voltage 208 VAC single-phase...
  • Page 42 Table 14. ONEAC Sinergy UPS (SE Series) North America SE61XA SE101XA SE203XA UPS Model (SE41XA*) (SE81*) (SE153XA*) Cooling Common Data (continued) Noise level mains operation < 50 dBa < 55 dBa <65 dBa Noise level battery operation < 55 dBa <65 dBa...
  • Page 43 Table 14. ONEAC Sinergy UPS (SE Series) North America SE61XA SE101XA SE203XA UPS Model (SE41XA*) (SE81*) (SE153XA*) hardwired hardwired hardwired Load connection min 8 AWG/6 mm min 6 AWG/10 mm 4 AWG/20 mm max 6 AWG/16 mm max 4 AWG/20 mm...
  • Page 44 Table 15. ONEAC Sinergy UPS (SE Series) (International) UPS Model SE61XI SE101XI Frequency with mains control see input frequency Frequency with internal control 50/60 Hz, ± 0.5% Distortion factor (linear/non-linear load) max. 4%/max. 7% Permissible crest factor 130% for 2 sec., 110% for 10 sec.
  • Page 45 Table 15. ONEAC Sinergy UPS (SE Series) (International) UPS Model SE61XI SE101XI RS232 interface Alarm contacts +5V...+12V Communications Signal input +5V...+12V Ethernet Connections hardwired hardwired Mains connections min 8 AWG/6 mm min 6 AWG * 10 mm max 6 AWG/16 mm...
  • Page 46: Battery Lifetime

    Figure 29 shows the typical lifetime of the batteries which are used in the UPS devices, depending on the devices’ ambient temperature. Optional Power Distribution Units (PDU) available for North American 4 -10 kVA. SPDU-2-0 SPDU-0-2 SPDU-1-0 SPDU-2-8 SPDU-2-4 SPDU-3-4 Fig. 30: Optional Power Distribution Units ONEAC Sinergy UPS User Manual...
  • Page 47: Typical Emergency Supply Times

    A700 Discharging Rating/VA S1000 S1000 A1000 A1000 1000 1000 Discharging Rating/VA Discharging Rating/VA Basic device + 1 battery extension Basic device + 2 battery extensions Fig. 31: Typical Emergency Runtimes for Sinergy S700 and S1000 ONEAC Sinergy UPS User Manual...
  • Page 48 A3000 1200 1800 2400 3000 1200 1800 2400 3000 Discharging Rating/VA Discharging Rating/VA Basic device + 1 battery extension Basic device + 1 battery extension Fig. 32: Typical Emergency Runtimes for Sinergy S2000 and S3000 ONEAC Sinergy UPS User Manual...
  • Page 49 Discharging Rating/VA Discharging Rating/VA S100 S100 E100 E100 + 1 battery extension 2000 4000 6000 8000 10000 2000 4000 6000 8000 10000 Discharging Rating/VA Discharging Rating/VA Fig. 33: Typical Emergency Runtimes for Sinergy SE61 and SE101 ONEAC Sinergy UPS User Manual...
  • Page 50 Fig. 34: Typical Emergency Runtimes for Sinergy SE203 and One Battery Pack Fig. 35: Typical Emergency Runtimes for Sinergy SE203 and Two Battery Packs ONEAC Sinergy UPS User Manual...