Camus Hydronics DynaMax DMH081 Installation, Operation And Service Manual page 70

Dynamax series gas fired wall hung & floor mount residential commercial stainless steel boilers
Table of Contents

Advertisement

Table 38: Manual Reset Error
Manual Reset Errors
Decimal
E2PROM_READ_ERROR
0
IGNIT_ERROR
1
GV_RELAY_ERROR
5
SAFETY_RELAY_ERROR
6
SPARE_LOCK_ERROR_1A
7
FAN_ERROR
8
RAM_ERROR
9
WRONG_EEPROM_SIGNATURE
10
E2PROM_ERROR
12
STATE_ERROR
13
ROM_ERROR
14
15MS_XRL_ERROR
16
SPARE_LOCK_ERROR_1D
17
T_MAX_LOCK_ERROR
18
STACK_ERROR
19
FLAME_OUT_TOO_LATE_ERROR
20
FLAME_ERROR_1
21
20MS_XRL_ERROR
22
41MS_ERROR
23
TOO_MANY_FLAME_FAILURES
24
FLAG_BYTE_INTEGRITY_ERROR
27
AD_HI_CPL_ERROR
28
AD_LO_CPL_ERROR
29
Hex
Description
0
No communication with E2Prom
Three unsuccessful ignition attempts in
1
a row
Problems with Gas Valve Relay =
5
Internal Hardware Error
Problems with Safety Relay = Internal
6
Hardware Error
7
Minimum fan speed < 1500 RPM,
8
Modulation signal not recognized
9
Internal software error
A
Contents of E2Prom are not up to date
C
No communication with E2Prom
D
Internal software error
E
Internal software error
10
Internal software error
11
12
High Limit tripped
13
Stack Limit tripped
Flame still present 10 sec. after closing
14
the gas valve
Flame detected just before gas valve
15
opened
16
Internal software error
17
Internal software error
Three times flame lost during one
18
demand
1B
Internal software error
1C
Internal software error
1D
Internal software error
Table 39: Automatic Reset Errors
Automatic Reset
Decimal
Errors
REFHI_TOO_LO_ERR
OR
31
REFHI_TOO_HI_ERRO
R
32
REFLO_TOO_LO_ERR
OR
33
REFLO_TOO_HI_ERR
OR
34
FLAME_ERROR_2
36
RETURN_TEMP_ERR
OR
40
WD_50HZ_ERROR
43
PHASE_ERROR
44
NET_FREQ_ERROR
45
FAULTY_EARTH_ERR
OR
46
WD_COMMUNICATI
ON_ERROR
47
APPLIANCE_SELECTI
ON_ERROR
48
T_SUPPLY_OPEN
51
T_RETURN_OPEN
52
T_DHW_OUT_OPEN
55
T_SYSTEM_OPEN
56
T_FLUE_OPEN
57
T_SUPPLY_SHORTED
59
T_RETURN_SHORTED
60
T_DHW_OUT_SHORT
ED
63
T_SYSTEM_SHORTED
54
T_FLUE_SHORTED
65
BLOCKED_FLUE_ERR
OR
66
FLOW_SWITCH_NOT
_OPEN_ERROR
67
FLOW_SWITCH_NOT
_CLOSED_ERROR
68
Hex
Description
1F
Internal hardware error
20
Internal hardware error
21
Internal hardware error
22
Internal hardware error
24
False Flame detected
Return temperature
28
exceeded 185oF
No ground connection,
or internal hardware
2B
error
Line and Neutral wires
2C
are interchanged
Line frequency differs
by more than 2% for
2D
60Hz
Ground connection
2E
fault
2F
Internal hardware error
Appliance selection
code and resistor do not
30
match upon startup
Supply sensor not
33
connected
Return sensor not
34
connected
DHW sensor not
37
connected
System sensor not
38
connected
Flue sensor not
39
connected
3B
Supply sensor shorted
3C
Return sensor shorted
3F
DHW sensor shorted
40
System sensor shorted
41
Flue sensor shorted
42
Blocked Flue condition
43
Flow switch not open
44
Flow switch not closed
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents