Camus Hydronics DynaMax DMH081 Installation, Operation And Service Manual page 10

Dynamax series gas fired wall hung & floor mount residential commercial stainless steel boilers
Table of Contents

Advertisement

Model
80
100
150
200
250
Depth Dim.
Model
"A" [in.]
80
16 1/2
100
16 1/2
150
16 1/2
200
23 1/2
250
23 1/2
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance
Table 2: DynaMax Wall Hung Service Clearances
Front
Top
24" (61cm)
3" (8 cm)
24" (61cm)
3" (8 cm)
24" (61cm)
3" (8 cm)
24" (61cm)
3" (8 cm)
24" (61cm)
3" (8 cm)
Figure 3: DynaMax Wall Hung Model Dimensions
Table 3: Appliance Dimensions and Specifications
Equivalent Length of Vent & Air
Intake Pipes at Recommended
Dim.
"B"
Over 25'
[in.]
and up to
100'
12
3
12
3
12
3
19
3
19
3
Service Clearance, Inches (cm)
Right Side
4" (10 cm)
4" (10 cm)
4" (10 cm)
4" (10 cm)
4" (10 cm)
Diameter, [in.]
Over 15'
and up to
Up to 15'
25'
3
2
3
2
3
2
3
2
3
2
Left Side
4" (10 cm)
0" (0 cm)
4" (10 cm)
0" (0 cm)
4" (10 cm)
0" (0 cm)
4" (10 cm)
0" (0 cm)
4" (10 cm)
0" (0 cm)
Water
Connection
Gas Connection
at Boiler
at Boiler [in.] NPT
[in.] NPT
1
1
1
1
1 1/4
Rear
1/2
1/2
1/2
1/2
1/2
5