Camus Hydronics DynaMax DMH081 Installation, Operation And Service Manual page 22

Dynamax series gas fired wall hung & floor mount residential commercial stainless steel boilers
Table of Contents

Advertisement

Table 11: Flow and Pressure Drop at a Given
Temperature Rise (Hydronic Heating)
30 ° F (16.7 °C)
Input,
Temp Rise
Btu/Hr
USGPM
∆ ∆ ∆ ∆ P Ft.
(min.
flow)
80,000
5.0
100,000
6.3
150,000
9.5
199,000
12.6
250,000
15.8
299,000
18.9
399,000
25.2
500,000
31.5
600,000
38.8
700,000
45.3
800,000
51.8
35 ° F (19.4 ° C)
Temp Rise
USGPM.
∆ ∆ ∆ ∆ P Ft.
(min.
flow)
8.2
4.3
6.2
12.3
5.4
9.4
10.4
8.1
7.8
7.2
10.8
5.8
11.5
13.5
8.7
9.3
16.2
7.0
8.4
21.6
6.3
9.2
27.0
6.9
17.5
32.0
11.8
18.2
40.0
14.4
23.5
43.0
16.0
DynaMax Floor Mount Piping Diagrams
Table 12: Flow and Pressure Drop at a Given
Temperature Rise (DHW)
20 °F (11.1 ° C)
Input,
Temp Rise
Btu/Hr
USGPM
(min.
flow)
80,000
7.5
100,000
9.4
150,000
14.0
199,000
19.2
250,000
23.5
299,000
28.8
399,000
38.4
500,000
48.6
600,000
57.6
700,000
70.4
800,000
77.6
∆ ∆ ∆ ∆ P Ft.
11.5
26.9
27.8
25.9
28.3
25.8
23.9
29.4
34.2
40.0
43.2
17