Specifications

In this section

UPS physical specifications...................................................................................................................... 43

ERM physical specifications..................................................................................................................... 43

UPS input specifications .......................................................................................................................... 43

UPS output specifications......................................................................................................................... 44
Battery specifications .............................................................................................................................. 45
Battery runtime for NA/JPN model ........................................................................................................... 45
Battery runtime for INTL model ................................................................................................................. 45
Environmental specifications .................................................................................................................... 46
REPO port specifications ......................................................................................................................... 46
UPS physical specifications
Parameter
Height
Depth
Width
Weight
ERM physical specifications
Parameter
Height
Depth
Width
Weight
UPS input specifications
NOTE: An asterisk (*) indicates the default setting.
UPS model
R5500 XR
NA/JPN
Value
13.03 cm (5.13 in)
66.04 cm (26 in)
44.15 cm (17.38 in)
68 kg (150 lb)
Value
13.03 cm (5.13 in)
63.83 cm (25.13 in)
44.45 cm (17.50 in)
75 kg (167 lb)
Utility voltage
Available settings utility
frequency (Hz)
voltage (VAC)
50/60
200/208*, 220, 230,
240
Dedicated
Line cord
branch circuit
rating (A)
30
Nondetachable power
cord with NEMA L6-30
plug
Specifications 43