Specifications; Mechanical; Electrical - Emerson GXT-RT series User Manual

Gxt-rt series 1~3kva ups
Table of Contents

Advertisement

Liebert GXTRT Series
1-3 kVA UPS
Chapter 5 Specifications

5.1 Mechanical

Power module GXT1000-RT
Power module GXT1000L-RT
Power module GXT2000-RT
Power module GXT2000L-RT
Power module GXT3000-RT
Power module GXT3000L-RT
Battery module GXT2000-BAT
Battery module GXT3000-BAT

5.2 Electrical

Model
Rating
Input system
Rated voltage
Voltage range
Frequency
Power factor
Output system
Power factor
Voltage
Line regulation
Load regulation
Voltage harmonic
distortion (rated
input voltage,
rated input
frequency)
Dynamic transient
response
Dynamic response
recovery
Frequency
Frequency
synchronization
speed
Page 25
Module
GXT
GXT
1000-RT
1000L-RT
1000VA/700W
0.99 (conditions: rated voltage, full pure resistive load, fully
220 Vac / 230 Vac / 240 Vac +/-2%
The output frequency synchronizes with the bypass frequency
when the bypass frequency is in the range of 50Hz±10%, with the
phase difference less than 3 degrees; the output frequency is
50Hz when the bypass frequency is outside specifications or the
bypass voltage is lower than 120Vac
W×H×D (mm)
440×87×400
440×87×400
440×87×400
440×87×400
440×87×400
440×87×400
440×87×400
440×87×400
GXT
GXT
2000-RT
2000L-RT
2000VA/1400W
1-phase, plus PE
220Vac / 230 Vac / 240 Vac
1. 176~288Vac, full load
2. <176Vac, linear derating
3. 120Vac, half load
50Hz±10%
charged battery)
1-phase, plus PE
0.7
≤2%(0~100% linear load)
≤2%(0~100% linear load)
≤2%(0 ~100% linear load)
≤5%(0 ~100% non-linear load)
IEC62040-3 Class 1
IEC62040-3 (60ms) Class 1
1 Hz/s
9/2005
Installation and User Manual

Specifications

Weight (kg)
17.5
7.8
8.6
9.6
9.0
10.0
20.5
21.5
GXT
GXT
3000-RT
3000L-RT
3000VA/2100W
Emerson Network Power