Alarm ID
Message Name
125
Control Hardware Problem
126
Control Internal Communication Problem
130
Configuration Jumper Missing
131
Corrupted Control Parameters
132
Failed Flash CRC Check (Check Sum) Software
is corrupted.
180
Outdoor Temperature Sensor Problem
200
Rollout Limit Switch Open
201
Indoor Blower Motor Problem
202
ID Blower Motor & Unit Size Mismatch
203
Invalid Unit Code
204
Gas Valve Problem
205
Gas Valve Relay Contact Closed
207
HSI Sensed Open
223
Low Pressure Switch Open
224
Low Pressure Switch Stuck Closed
225
High Pressure Switch Failed to Close
226
High Pressure Switch Stuck Closed
227
Low Pressure Switch Open in Run Mode
228
Inducer/Pressure Switch Calibration Failure
240
Low Flame Current − Run Mode
506052−01 11/09
Alarm Codes and Troubleshooting
Action required to Clear/Recover
Hardware problem on the control board. Cycle power on control. Replace if problem prevents service and is
persistent.
Hardware problem on the control board. Cycle power on control. Replace if problem prevents service and is
persistent.
Configuration jumper(s) missing on control board (applicable in non−communication only).
Reconfigure the system. Replace board if service (heating cooling) is not viable.
Recycle power, if re−occurs replace control.
Compare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace if
necessary.
Correct unit cause of rollout trip or replace flame rollout switch and test furnace operation.
Indoor blower communication failure including power outage. Check wiring to motor.
Incorrect appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air
Handler on configuration guide or in installation instructions.
No appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air
Handler on configuration guide or in installation instructions.
Check operation and wiring of gas valve.
Check wiring to relay; if wiring is correct, replace relay.
Measure resistance of Hot Surface Ignition ignitor. Replace if open or not within specification range found in
IOM.
Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-
ating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check inches of water column closing pressure of high pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check operation of high pressure switch for closing on heat call, measure inches of water column of operating
pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Unable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.
Check micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.
Measure voltage of neutral to ground for good unit ground.
Page 32
table continued on next page