Lennox icomfort Setup Manual page 27

Touch screen programmable communicating thermostat
Hide thumbs Also See for icomfort:
Table of Contents

Advertisement

Parameter Name:
AIR HANDLER
Equipment Name
Electric Heating Airflow
Low Cooling Airflow
High Cooling Airflow
Cooling Airflow Profile
Low Heating Airflow
High Heating Airflow
Continuous Indoor Blower Airflow
Humidification Airflow
Dehumidification Airflow
Heating Indoor Blower OFF Delay
Heating Indoor Blower ON Delay
Cooling Indoor Blower OFF Delay
Cooling Indoor Blower ON Delay
HP Indoor Blower OFF Delay
HP Indoor Blower ON Delay
THERMOSTAT
Equipment Name
Temp Reading Calibration
Humidity Reading Calibration
OUTDOOR EQUIPMENT
Equipment Name (HP and AC)
Compressor Short Cycle Delay (HP and AC)
Compressor Shift Delay On/Off (HP only)
Defrost Termination Temp (HP only)
Default
Air Handler
nnnn CFM
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
SEE NOTE −.
1: No Delays,
1
2: ON: No delays; OFF: 45 sec delay
nnnn CFM
NOTE: CFM Default and Values Settings are dependent on the tonnage of the unit
SEE NOTE −.
70%
60 to 80% (percentage of reduction of High Cooling Airflow)
10 sec
0 sec
0 sec
2 sec
45 sec
0 sec
0ºF
0%
Outdoor Unit
(Typewriter input screen = up to 35 characters in string)
300 Seconds
On
50ºF
Page 27
Parameter Value Setting
(Typewriter input screen)
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min; OFF:50%/30s
0 to 10 Seconds
0 to 5 Seconds
0 to 30 Seconds
0 to 10 Seconds
0 to 60 Seconds
0 to 30 Seconds
(Typewriter input screen)
−5ºF to 5ºF
−10 to 10%
60 to 300 Seconds
On, Off
50 to 100ºF
icomfortt Touch Screen 7−Day Programmable Thermostat
Increment
5CFM
5CFM
5CFM
5CFM
5CFM
10CFM
10CFM
1%
1 sec
1 sec
2 sec
1 sec
5 sec
5 sec
1ºF
1%RH
60 Sec
10ºF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Icomfort touch

Table of Contents