Vesda driver
Hide thumbs Also See for FS-8700-43 VESDA:
Table of Contents

Advertisement

FS-8700-43 VESDA Driver Manual
Data Block 1 Description
BIT offset
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Data Block 2 Description
FLOAT offset
0
6
1 indicates TRUE; 0 indicates FALSE
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
6
Reserved Flash
Fault Filter Flash
Fault Airflow Flash
Fault Network Flash
Fault Power Flash
Fault Urgent Flash
Fault Zone Flash
Fault System Flash
OK Flash
Isolate Flash
Fault Minor Flash
Fault Major Flash
Alarm Fire2 Flash
Alarm Fire1 Flash
Alarm Action Flash
Alarm Alert Flash
Reserved
Fault Filter
Fault Airflow
Fault Network
Fault Power
Fault Urgent
Fault Zone
Fault System
OK
Isolate
Fault Minor
Fault Major
Alarm Fire2
Alarm Fire1
Alarm Action
Alarm Alert
Function
Average Smoke Level (Sector must be set to zero)