Specifications
Ceiling Mounted Built-in Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel Color
Panel
Dimensions: (H×W×D)
(Option)
Weight
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
2 Nominal heating capacities are based on the following conditions:
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
16
FXSQ30MVJU
Btu/h
30,000
Btu/h
34,000
Galvanized Steel Plate
in
11-7/8 × 55-1/8 × 31-1/2
3 × 14 × 14
ft²
3.64
3D18H2A
Sirocco Fan
HP
0.30
cfm
950/720
4
in. Aq
0.57-0.39
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
in
3/8 (Flare Connection)
φ
in
5/8 (Flare Connection)
VP25
in
(External Dia. 1-1/4 Internal Dia. 1)
Lbs
119
dBA
45/39
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
BYBS125DJW1
White (10Y9/0.5)
in
2-1/8 × 59 × 19-5/8
Lbs
14
Operation Manual, Installation
Manual, Paper Pattern for
Installation, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing
Pads, Clamps, Screws, Washers.
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
means
"High static pressure – Standard".
these values are normally somewhat higher as a result of installation conditions.
FXSQ36MVJU
36,000
40,000
Galvanized Steel Plate
11-7/8 × 55-1/8 × 31-1/2
3 × 14 × 14
3.64
3D18H2A
Sirocco Fan
0.30
990/740
0.57-0.35
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
3/8 (Flare Connection)
φ
5/8 (Flare Connection)
VP25
(External Dia. 1-1/4 Internal Dia. 1)
119
45/39
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
BYBS125DJW1
White (10Y9/0.5)
2-1/8 × 59 × 19-5/8
14
Operation Manual, Installation
Manual, Paper Pattern for
Installation, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing
Pads, Clamps, Screws, Washers.
C:3D042684
SiUS39-602
FXSQ48MVJU
48,000
54,000
Galvanized Steel Plate
11-7/8 × 55-1/8 × 31-1/2
3 × 14 × 14
3.64
3D18H2A
Sirocco Fan
0.30
1,300/950
0.34-0.10
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
3/8 (Flare Connection)
φ
5/8 (Flare Connection)
VP25
(External Dia. 1-1/4 Internal Dia. 1)
122
48/43
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
BYBS125DJW1
White (10Y9/0.5)
2-1/8 × 59 × 19-5/8
14
Operation Manual, Installation
Manual, Paper Pattern for
Installation, Drain Hose, Clamp
Metal, Insulation for Fitting, Sealing
Pads, Clamps, Screws, Washers.
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents