J3" Outdoor Unit: Malfunction Of Discharge Pipe Thermistor (R31~32T) - Daikin REYQ72 Serveice Manual

R-410a heat recovery 60hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.25 " J3 " Outdoor Unit:
Thermistor (R31~32T)
J3
Remote
Controller
Display
Applicable
REYQ72M, 96M
Models
Method of
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Detection
Malfunction
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
The alarm indicator is displayed when the fan is being used also.
156
Malfunction of Discharge Pipe
Defect of thermistor (R31T, R32T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to X34A
of outdoor unit
PC board
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R31, 32T from the outdoor
unit PC board.
(3.5kΩ~
400kΩ)
YES
NO
NO
SiUS39-602
Connect the thermistor and turn
on again.
Replace the thermistor (R31, 32T)
Replace outdoor unit PC board
(A1P).
Troubleshooting
(V3072)