SiUS39-602
5.3

Demand Operation

In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using "Demand 1 Setting" or "Demand 2 Setting".
To operate the unit with this mode, additional setting of "Continuous Demand Setting" or
external input by external control adapter is required.
[Demand 1 setting]
Demand 1 setting 1
Demand 1 setting 2 (factory setting)
Demand 1 setting 3
[Demand 2 setting]
Demand 2 setting 2 (factory setting)
5.4

Heating Operation Prohibition

Heating operation is prohibited above 24°C ambient temperature.
Function
Setting
Setting
Other protection control functions have precedence over the above operation.
Standard for upper limit of power consumption
Approx. 80%
Approx. 70%
Approx. 60%
Standard for upper limit of power consumption
Approx. 40%
Other Control
67