Address Duplication, Improper Setting; Mc" Address Duplication, Improper Setting - Daikin REYQ72 Serveice Manual

R-410a heat recovery 60hz
Table of Contents

Advertisement

SiUS39-602
" MC "
4.5

Address Duplication, Improper Setting

MC
Remote
Controller
Display
Applicable
Schedule timer
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
When two or more schedule timers are connected.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Address duplication of schedule timer
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Are two or more
schedule timer
connected?
NO
Troubleshooting (OP: Schedule Timer)
YES
Disconnect all schedule timer
except one and reset the
centralized controller timer's
power supply.
Reset the power supply for the
schedule timer.
(V2840)
205

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents