Field Setting
The following settings are made by pushbutton switches on PC board.
There are the following three setting modes.
Initial status (when normal) : Indicates during "abnormal", "low noise control" and "demand
control".
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Used to check the program made in Setting mode 2.
Press BS1 (MODE button) for more than 5 sec.
Setting mode 2
Setting item selection
(SET button)
Press BS3
(RETURN button).
Setting condition
selection (SET button)
Press BS3
(RETURN button).
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS1
(MODE button).
92

Setting by pushbutton switches

Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
Mode changing procedure
BS1
BS2
BS3
BS4
MODE
SET
RETURN
TEST
(Normal)
Setting mode 1
MODE
Off
H1P
(Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1(MODE button).
(Initial condition)
BS5
RESET
(V2760)
Push the BS1(MODE button)
one time.
Monitor mode
MODE
H1P
Monitor mode
Setting item selection
(SET button)
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Press BS1
(MODE button).
Test Operation
SiUS39-602
Blinking
(V2761)
(V2762)