Unit Mode Listed As Standby - Trane UniTrane Installation Operation & Maintenance

Fan-coil room conditioners force flo cabinet heaters low vertical fan-coils
Table of Contents

Advertisement

Cycling Power to the
TUC
Using Tracer 100i
100L
Using Tracer Summit
Unit Mode Listed
as Standby
108
Remove the 24 VAC power from the board and then reapply it to
cycle the unit through a power-up sequence. By default, the controller
attempts to reset all diagnostics at power-up.
or
The TUC editor's reset failure point allows the user to reset controller
diagnostics. Also, Tracer
enter" option from the TUC service summary screens that allow
latching diagnostic reset.
®
When using a Tracer Summit
the reset diagnostics button on the TUC editor screen.
The unit's operating machine state is in standby when one of the
following conditions occurs:
1. Tracer
®
override is present.
2. During the power-up sequence or any time when the TUC is
calibrating its end devices.
3. When the TUC is in the unoccupied mode and there is no call for
heating or cooling.
4. In the occupied mode when the desired capacity is unavailable.
ie: the TUC requests a 2-pipe unit to heat, yet no hot water or electric
heat is available. The TUC will list the unit as being in standby mode.
Terminal Unit
Control (TUC)
®
versions 14.4 and higher provide a "+
®
system, reset the unit diagnostics with
UNT-IOM-6