Trane UniTrane Installation Operation & Maintenance page 84

Fan-coil room conditioners force flo cabinet heaters low vertical fan-coils
Table of Contents

Advertisement

Manual Output Test
Test Sequence
Table 34. Test Sequence
Step
Fan
J1-1
1
1: Off
Off
2: Fan High
2
High
3: Fan Med
Off
4: Fan low
Off
5: Main open
High
6: Main close,
High
EH1 on
7: Aux open,
High
EH1 on
8: Aux close,
High
EH1 off, EH2 on,
damper open
9: Damper close High
10: Generic/
High
baseboard
heat energized
6
11: Exit
Exit
1
Upon entering manual output test mode, the controller turns off all fan and electric heat outputs and drives
LED Operation
84
The procedure for testing is:
1.Press and hold the Test button for at least two seconds, then
release the button to start the test mode. When manual output test
mode begins, the controller turns off all outputs and calibrates
modulating end devices closed.
2. Press the Test button (no more than once per second) to advance
through the test sequence. Alternatively, the manual output test can
be controlled over the communications network by using Rover™.
Main valve
J1-2
J1-3
J1-5
Off
Off
Off
On
Off
Off
Off
Off
Med
Off
Off
Off
Off
Low
Off
Off
Off
Off
On
Off
Off
Off
Off
On
Exh
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
The green status LED is off when you press the Test button.To begin
the manual output test mode, press and hold the Test button (which
causes the green LED to go off) for at least two seconds, then
release the button.The green LED blinks, indicating the controller is in
manual test mode.
Tracer
Electric heat
Fresh
or aux. valve
air
damper
J1-6
J1-9
J1-10
J1-11
Off
aux: on Off
EH: off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
On
Off
Off
Off
On
On
Off
Off
Off
Off
Off
Off
®
ZN.520
Generic/
baseboard
heat
J1-12
TB4-1
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
On
UNT-IOM-6