Trane UniTrane Installation Operation & Maintenance page 71

Fan-coil room conditioners force flo cabinet heaters low vertical fan-coils
Table of Contents

Advertisement

UNT-IOM-6
to expose the damper stop screw on the control panel end. Relocate
the stop screw to the appropriate position. Then loosen the stop
screw wingnut and adjust the linkage.
Economizer Damper
With a valid outdoor air temperature (either hardwired or communi-
cated), Tracer
®
ZN.520 uses the modulating economizer damper as
the highest priority source of cooling. Economizer operation is only
possible through the use of a modulating damper.
Economizing is possible during the occupied, occupied standby,
unoccupied, and occupied bypass modes.
The controller initiates the economizer function if the outdoor air
temperature is cold enough to be used as free cooling capacity. If the
outdoor air temperature is less than the economizer enable setpoint
(absolute dry bulb), the controller modulates the outdoor air damper
(between the active minimum damper position and 100%) to control
the amount of outdoor air cooling capacity. When the outdoor air
temperature rises 5 F above the economizer enable point, the control-
ler disables economizing and moves the outdoor air damper back to
its predetermined minimum position based on the current occupancy
mode or communicated minimum damper position.
Table 25. Relationship Between Outdoor Temperature Sensors
and Damper Position
Outdoor Air Temp.
Modulating Outdoor Air Damper
Occ. or
Occ. bypass
None or invalid
Open to occ.
min.pos.
Failed
Open to occ.
min.pos.
Present and econ.
Economizing:
feasible
min pos.-100% between occ.
Present and econ.
Open to occ.
not feasible
min. pos.
®
Tracer
ZN.520
Occ. standby
Unocc.
Open to occ.
Closed
standby
min. pos.
Open to occ.
Closed
standby
min. pos.
Economizing:
Open and
econ. only
standby min.
when unit
pos.-100%
operating,
closed
otherwise
Open to occ.
Closed
standby
min. pos.
71