Table 20. Fresh Air Damper Stays Open
Probable Cause
Normal Operation
Manual Output Test
Unit Configuration
Unit Wiring
58
Explanation
The controller opens and closes the fresh air damper based on the controller's
occupancy mode and fan status. Normally, the fresh air damper is open during
occupied mode when the fan is running and closed during unoccupied mode.
The controller includes a manual output test sequence that verifies analog and
binary output operation and associated wiring. However, based on the current
step in the test sequence, the fresh air damper may be open. Refer to the
"Manual Output Test" section on page 51.
The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the actual
end device, the damper may not work correctly.
The wiring between the controller outputs and the fresh air damper must be
present and correct for normal damper operation. Refer to the typical unit wiring
diagrams in the Appendix of this manual.
®
Tracer
ZN.010
and ZN.510
UNT-IOM-6