Binary Outputs
74
Binary outputs are configured to support the following:
• Three fan stages (when one or two fan stages are present, medium
fan speed can be configured as exhaust fan)
• One hydronic cooling stage
• One hydronic heating stage (dehumidification requires this to be in
the reheat position)
• One DX cooling stage
• One- or two-stage electric heat (dehumidification requires this to be
in the reheat position)
• Face and bypass damper
• Modulating outdoor air damper
• One baseboard heat stage
Table 27. Binary Output Configuration
Binary Output
Configuration
J1-1
Fan high
J1-2
Fan medium
J1-3
Fan low
J1-4
(Key)
J1-5
Cool valve – open, or 2 position valve,
(Note 1)
J1-6
Cool valve – close (Note 1)
J1-9
Heat valve – open, or 2 position valve, or 1
Electric heat stage (Note 1)
J1-10
Heat valve – close or 2
(Note 1)
J1-11
Fresh air damper - open
J1-12
Fresh air damper - close
TB4-1
Generic / Bbaseboard heat output
TB4-2
24VAC
Note 1: For Tracer
®
ZN.520 units configured and applied as 2-pipe
hydronic heat/cool changeover, terminals J1-5 and J1-6 are used to
control the primary valve for both heating and cooling. For Tracer
ZN.520 units configured and applied as 2-pipe hydronic heat/cool
changeover with electric heat, terminals J1-5 and J1-6 are used to
control the primary valve (for both cooling and heating), and terminals
J1-9 and J1-10 are used only for the electric heat stage. For those 2-
pipe changeover units, electric heat will not be energized while the
hydronic supply is hot (5 or more degrees above the space tempera-
ture).
®
Tracer
ZN.520
nd
Electric heat stage
UNT-IOM-6