Page 1
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. July 2020 SRV-SVN06C-EN...
Page 2
CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs. Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules.
Page 3
Non-Trane personnel should always follow local regulations. Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Electric Heater Overview Introduction This installation manual covers the 50 kW and 150 kW electric heaters available to rent from Trane Rental Services for temporary heating solutions. It includes heater technical information, start-up information and unit maintenance. The information contained in this bulletin is provided to ensure the safe installation and operation of the equipment and its surroundings.
Use a forklift of suitable capacity to move the unit. Failure to properly lift unit could result in death or serious injury or possible equipment or property only damage. Figure 1. 50 kW Electric Heater Figure 2. 150 kW (F0) Electric Heater SRV-SVN06C-EN...
Page 8
Figure 3. 150 kW (F1) Electric Heater SRV-SVN06C-EN...
Motor FLA Unit FLA 56.6 187.5 * The 150 kW (F1) heater has two stages of heat and can be used as a 75 kW heater. In this scenario, the unit FLA is 92 amps and MOP is 150 amps. SRV-SVN06C-EN...
Note: At least one section of duct must be connected to the supply or return of the 50 kW electric heater to prevent the fan breaker from tripping due to excessive fan speed. Figure 4. 50 kW Control Panel Figure 5. 150 kW (F0) Control Panel SRV-SVN06C-EN...
VFD Fault – indicates internal problem on VFD. Refer to manufacture’s manual for troubleshooting procedures. (NOTE: Pushing the Emergency Stop Button will shut down the VFD and indicate VFD FAULT. 480V power must be removed to reset this fault.) SRV-SVN06C-EN...
Note: If the Power LED is illuminated, the unit is ready for operation. If not, check the unit supply voltage at the main power source. Disconnect (turn off) the unit’s circuit breaker and the main power at the power source when checking voltage. SRV-SVN06C-EN...
Note: Hi limit fault and air limit fault lights will operate until the air flow is sufficient to remove the faults – these faults will turn off within 2-3 seconds after fan operates! • Push each fault light button to verify all fault lights function correctly. SRV-SVN06C-EN...
Page 17
Installation/Start-up Guidelines • Adjust outlet temperature and fan speed to obtain desired heating performance (Do not attempt to set outlet temperature above 300°F). • Close all covers (local and remote panels) and secure. SRV-SVN06C-EN...
Each unit is provided with cleanable filters that are installed in the evaporator return air section. The return air grill must be removed to gain access to the filters. Check filters periodically to verify that they are clean. The filters can be cleaned by rinsing them with water. SRV-SVN06C-EN...
Page 20
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.