Capacity Correction Factor By The Length Of Refrigerant Piping (Reference) - Daikin J-Series Engineeiring Data

J-series split cooling only / heat pump
Hide thumbs Also See for J-Series:
Table of Contents

Advertisement

Capacity Tables
7.3

Capacity correction factor by the length of refrigerant piping (Reference)

The cooling and the heating capacity of the unit has to be
corrected in accordance with the length of refrigerant piping. (The
<— line : cooling capacity>
<--- line : heating capacity>
R-410A (09/12 class)
1
0.9
0.8
16.4
Piping length (ft)
The graph shows the factor when additional refrigerant of the
proper quantity is charged.
18
Range of the refrigerant
additional charge
32.8
49.2
(R11493)
distance between the indoor unit and the outdoor unit)
Note:
EDUS041016
Room Air Conditioners J-Series