  • Page 1: Installation Manual

    DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel d’installation Manual de instalación MODELS FTXS09JEVJU FTXN09JEVJU FTXS12JEVJU FTXN12JEVJU FTKS09JEVJU FTKN09JEVJU FTKS12JEVJU FTKN12JEVJU...
  • Page 2: Safety Precautions

    Safety Precautions • Read these Safety Precautions carefully to ensure correct installation. • This manual classifies the precautions into DANGER, WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety. DANGER ..Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING ..Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
  • Page 3: Choosing An Installation Site

    Safety Precautions WARNING • During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury. •...
  • Page 4: Preparation Before Installation

    Preparation before Installation Removing and installing front panel • Removal method Hook fingers on the tabs on the left and right of the main body, and open until the panel stops. Slide the front panel sideways to disengage the rotating shaft. Then pull the front panel toward you to remove it. •...
  • Page 5: Indoor Unit Installation Drawings

    Indoor Unit Installation Drawings How to attach the indoor unit Mounting Hook the claws of the bottom frame plate to the mounting plate. If the claws are difficult to hook, remove the front grille. Clip How to remove the indoor unit Mounting plate Push up the marked area (at the lower part of the front grille) to...
  • Page 6: Installing The Mounting Plate

    Indoor Unit Installation Installing the mounting plate • The mounting plate should be installed on a wall which can support the weight of the indoor unit. 1) Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the boring points on the wall.
  • Page 7: Boring A Wall Hole And Installing Wall Embedded Pipe

    Indoor Unit Installation Boring a wall hole and installing wall embedded pipe • For walls containing metal frame or metal board, be sure to use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire. Inside Outside Wall embedded pipe...
  • Page 8: Left-Side, Left-Back, Or Left-Bottom Piping

    3-2. Left-side, left-back, or left-bottom piping How to replace the drain plug and drain hose • Replacing onto the left side Drain hose attachment position * The drain hose is on the back of the unit. 1) Remove the insulation fixing screws on the right and remove the drain hose.
  • Page 9 Indoor Unit Installation Wiring 1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto the conduit mounting plate. 2) Strip wire ends (9/16 inch (15mm)). 3) Match wire colors with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the corresponding terminals.
  • Page 10 5-5. Prepare the accessory (separate product) [Figure 2]. 1) Remove the cover from the accessory (separate product). 2) Insert the connection cord into connector “S21” (white) in the accessory (separate product). 3) Route each of the connection cords through the cut-outs in the accessory, then reinstall the accessory cover in its original position.
  • Page 11: Drain Piping

    Indoor Unit Installation Drain piping The drain hose should be inclined downward. 1) Connect the drain hose, as described right. No trap is permitted. Do not put the end of the hose in water. 2) Remove the air filters and pour some water into the drain pan to check the water flows smoothly.
  • Page 12: Refrigerant Piping

    Refrigerant piping CAUTION • Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.) • To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.) •...
  • Page 13: Trial Operation And Testing

    Trial Operation and Testing Trial operation and testing 1-1 Measure the supply voltage and make sure that it falls in the specified range. 1-2 Trial operation should be carried out in either cooling or heating mode. For Heat pump • In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature.