DIGITALCONTROi PANEilicD SEQUENCE
START SEQUENCE
With the pre,start inspection completed, press the START
button and the automatic sequence will begin. The six
indicator lights will illuminate green and the panel will
display the following text:
.
. Waiting for operator
f'WIWESTERBEKE
Press start to
, EngInes
&
Generalor.s
-
engage generator
Pre l'Ieating ......
Cr.nking ......
7 Seconds
RUN SEQUENCE· . . . .
As the display cycles thru the engine functions, the speed
will come np to 1800 rpms-60Hz (1500 rpms-50Hz) and
the oil pressure and engine coolanJ will rise to their nonnal
readings. The functions will cycle in the following sequemce:
'Englne Speed
.Co"lant Temperature
1800
RPM
81C
17~f.
250J,
32',
0
!
0
1~tr·
.'
....
_.
S¢J~PLl
.
-._-
SCROLL
Batt\ry Voltage
Oil
Pressure." ' ..
13.5voo
3.1
40
·B:A.R'
PSI'.
!
" .0
1Q.Q
0
30
0
.6~9
.
,._I:l.CROLL
SCROLL
Engine Hours
. AC Frequency
3,8
HOURS
0
60,1Hz
100
!
."
SCROLL
SCROLL
AC Line Voltage
~i
120V o
~~i<;
.
SCROLL LOCK
To stop the continuing sequence, press the
TTl
button. This ellllbies the operator to monitor a single function
for any length of time. The word LOCK will appear in the
COfl)!lr. Use the up and down arrows
to
find and observe other
functions. To resume scrolling, press the SCROLL LOCK
button again.
.
STOP SEQUENCE
To stop the generator, press the STOP button. The display
will cycle
thru
the following text messages and shutdown.
Shutting'
110w,;' . .
Engine Shutdown
Waiting for operator
Press' start to
engag.e generator
FAILURE LIGHT/SHUTDOWN
If a problem occurs, the generator will shutdown and the .
FAILURE light will illwninate red.
In
addition, one of the
indicator lights will change from green to orange to reveal
where the ttouble has occured and the display will text
message what has happened.
.
Examples:
Failure Light is
red.
CPQl.aill;Temperature Light
"is orange," .
Failure Light is
red.
High Engine Temp.
Reset ECU to Restart'
Low
Oil
Pressure
Oil Pressure Light is
or~nge.
Reset ECO to Restart
When a failure occurs, refer to thetroubleshooting chari;
wiring diagram, and general operating text in this manual to
assist in solving the trouble.
There are many combinations of messages that can be
displayed but they are all self explanatory and the operator
can easily isolate and correct the problem should one occur.
Before re-starting the generator, tlie 20 amp DC circuit
breaker' must be reset. With the problem corrected and the
generator started, the sequences will begin cycling again.
A
NOTE: Three phase voltages will vary depending on the AC
\l
output configuration of the generator.
Conlrol Box Components
t
and
Frequency Adjustments.
' .
are on Ihe following pag •.
"'loY'
WESTERBEKE
Engines & Generators
7A