Factory Built Zero Clearance Fireplace - Quadra-Fire 5100I-GD-B Owner's Manual

5100-i act wood insert advanced combustion technology (act)
Hide thumbs Also See for Quadra-Fire 5100I-GD-B:
Table of Contents

Advertisement

R
G. Factory-Built Zero Clearance Fireplace
(USA INSTALLATIONS ONLY)
The Quadra-Fire 5100-I Insert is listed to UL 18 Standard
and is approved for installation into listed factory-built zero
clearance fireplaces listed to UL 1 conforming to the follow-
ing specifications and instructions:
The original factory-built clearance fireplace chimney cap
must be re-installed after installing the approved chimney
liner meeting type H.T. requirements (100°F) per UL 1.
The air flow of the factory-built zero-clearance fireplace
system must not be altered. The flue liner top support attach-
ment must not reduce the air flow for the existing air-cooled
chimney system.
NOTE: Refer to chimney liner manufacturer for recom-
mendations on supporting the liner.
Minimum Width of cavity opening:
Minimum Height:
Minimum Depth from front to rear:
The factory-built chimney must be listed per UL1 and meet
the type HT requirements of UL10. Factory-built fireplace
chimneys tested to UL1-1998, may be at the fireplace
manufacturer's option, tested to the same criteria as UL10
HT requirements. If the chimney is not listed as meeting HT
requirements, or if the factory-built fireplace was tested prior
to 1998, a full height listed chimney liner must be installed
from the appliance flue collar to the chimney top. The liner
must meet type HT requirements (100ºF) per UL 1.
The liner must be securely attached to the insert flue collar
and the chimney top. To prevent room air passage to the
chimney cavity of the fireplace, seal either the damper area
around the chimney liner with high temperature sealant or
the fireplace front with fiberglass batting. Circulating air
chambers (i.e. in a steel fireplace liner or metal heat circula-
tor) may not be blocked.
Page 18
5100-I ACT WOOD INSERT
36 in.
24 in.
19 in.
Flue Liner with Required Air Space
Stainless Steel Chimney Connector
Must Extend to Flue Liner
Minimum 8" (203mm) Masonry Thickness
in Front of Smoke Chamber
Minimum Clearance in Accordance with
Insert Listing
Floor Protection in
Accordance with Insert
Combustible Floor
Figure 18.1
The fireplace must not be altered, except that the damper
may be removed to accommodate a direct-connect starter
pipe or chimney liner, and external trim pieces which do not
affect the operation of the fireplace may be removed provid-
ing they can be stored on or within the fireplace for reassem-
bly if the insert is removed.
The following modifications of factory-built fireplaces are
permissible:
• removal of damper
• removal of smoke shelf or baffle
• removal of ember catches
• removal of fire grate
• removal of viewing screen/curtain
• removal of doors.
The permanent metal warning label provided must be
attached to the back of the fireplace, with screws or nails,
stating that the fireplace may have been altered to accom-
modate the insert, and must be returned to original condition
for use as a conventional fireplace.
Final approval of this installation type is contingent upon
the authority having jurisdiction.
Fire Risk.
When lining air-cooled factory-built chimneys:.
• Re-install original factory built chimney cap
Listing
438-0380D
WARNING
Run chimney liner approved to UL 1 Type
HT requirements (100 degrees F)
ONLY
DO NOT block cooling air openings in chimney
Blocking cooling air will overheat the chimney
Airtight Insulated Clean-Out
Damper Plate Removed or
Fastened in Open Position
Seal with Non-Combustible Material
September 1, 2008