Chimney Termination Requirements; 2-10-3 Rule - Quadra-Fire 5100I-GD-B Owner's Manual

5100-i act wood insert advanced combustion technology (act)
Hide thumbs Also See for Quadra-Fire 5100I-GD-B:
Table of Contents

Advertisement

R
D. Chimney Termination Requirements
Follow manufacturers instructions for clearances, securing,
flashing and terminating the chimney.
Must have an approved and listed cap
Must not be located where it will become plugged by
snow or other material
Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
Must be located away from trees or other structures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper flue draft
3 in. (91cm)
Minimum
Figure 16.1
Figure 16.2
Page 16
2 ft. (61cm)
10' (305cm) To Nearest Roofline
10 ft. (305cm) or more
Wall or Parapet
3 ft. (91cm) Minimum
5100-I ACT WOOD INSERT
NOTE:
• Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
Pitched Roof
3 ft. (91cm) Minimum
Flat Roof
438-0380D
Less than 10 ft. (305cm)
2 ft. (61cm)
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
September 1, 2008