Section 1: Listing And Code Approvals; Appliance Certification; Mobile Home Approved - Heatilator CONSTITUTION C-40 Owner's Manual

Epa certified woodburning fireplace installation and operation
Hide thumbs Also See for CONSTITUTION C-40:
Table of Contents

Advertisement

1
Listing and Code Approvals
A. Appliance Certification
Model:
Constitution EPA Certified
Woodburning Fireplace
Laboratory:
OMNI Test Laboratories, Inc.
Report No:
061-S-50-2
Type:
Wood Fireplace
Standard:
UL127 and ULC-S610-M87 and
(UM) 84-HUD, Mobile Home
Approved.
This fireplace system has been tested and listed in
accordance with UL127 and ULC-S610-M87 standards,
and has been listed by OMNI Test Laboratories, Inc., for
installation and operation in the United States and Canada
as described in this manual. This fireplace has been tested
and listed for use with the SL-300 Series chimney (with
the the CAK4A Air Kit) and fireplace components listed in
Section 12.
Check with your local building code agency before you begin
your installation to ensure compliance with local codes,
including the need for permits and follow-up inspections. Be
sure local building codes do not supersede UL specifications
and always obtain a building permit so that insurance protec-
tion benefits cannot be unexpectedly cancelled.
B. Mobile Home Approved
This appliance is approved for mobile home installations
when not installed in a sleeping room and when an outside
combustion air inlet is provided. The structural integrity of
the mobile home floor, ceiling, and walls must be maintained.
The fireplace must be properly grounded to the frame of the
mobile home and use only listed double-wall connector pipe.
Outside Air must be installed in a mobile home installation.
An outside air termination cap is supplied with your
Constitution Fireplace for installation in a mobile home.
If you use an alternative material it must be designed to
prevent material from dropping into the area beneath
the mobile home, and to prevent rodents from entering
from the outside.
1. An outside air inlet must be provided for combustion and
must remain clear of leaves, debris, ice and/or snow. It
must be unrestricted while unit is in use to prevent room air
starvation which can cause smoke spillage and an inability
to maintain a fire. Smoke spillage can also set off smoke
alarms.
Page 4
Heatilator • Constitution EPA Fireplace • 480-1091C
2. The fireplace is to be secured to the mobile home structure.
Use same holes that attached the fireplace to the pallet to
secure it to the floor using 1/4 in. x 2 in. (6 mm x 51 mm)
lag bolts or equivalent.
3. Unit must be grounded with #8 solid copper grounding
wire or equivalent and terminated at each end with N.E.C.
approved grounding device.
4. Refer to Minimum Clearances to Combustibles on pages
11-12 and chimney components on pages 64-65.
5. Floor protections requirements on pages 38-40 must be
followed precisely.
6. Use silicone to create an effective vapor barrier at the
location where the chimney or other component penetrates
to the exterior of the structure.
7. Follow the chimney and chimney connector manufacturer's
instructions when installing the flue system for use in a mobile
home.
8. If unit burns poorly while an exhaust fan is on in home,
(i.e., range hood), increase combustion air.
NOTE: Top sections of chimney must be removable to
allow maximum clearance of 13.5 ft (411 cm) from ground
level for transportation purposes.
Fire Risk.
For use with solid wood fuel only.
Other fuels may overfire and generate
poisonous gases (i.e. carbon monoxide).
Maintain structural integrity of mobile home:
• Floor, wall, ceiling and/or roof.
Do NOT cut through:
• Floor joist, wall, studs or ceiling trusses.
• Any supporting material that would affect the structural
integrity.
Asphyxiation Risk.
Never install in a sleeping room.
Consumes oxygen in the room.
WARNING
CAUTION
WARNING
November 11, 2008