Install The Attic Insulation Shield; Double-Check The Chimney Assembly; Secure The Chimney - Heatilator CONSTITUTION C-40 Owner's Manual

Epa certified woodburning fireplace installation and operation
Hide thumbs Also See for CONSTITUTION C-40:
Table of Contents

Advertisement

G. Install the Attic Insulation Shield
An insulation shield must be installed when there is a pos-
sibility of insulation coming into contact with the factory built
chimney system.
Bend the tabs at the top of the attic insulation shield inward.
This will help keep the chimney section centered in the
shield.
Position the shield over the vertical chimney section where
it penetrates a ceiling firestop.
• Slide the shield down until it rests on the ceiling firestop.
The ceiling firestop will support the insulation shield. See
Figures 24.1 and 24.2.
WARNING
Fire Risk
• DO NOT pack insulation or other
combustibles: between ceiling firestops;
between chimney and attic insulation
shield.
• ALWAYS maintain specified clearances around chimney
and ceiling firestop systems.
• Install ceiling firestops as specified.
Failure to keep insulation or other material away from
chimney pipe may cause fire.
H. Double-check the Chimney Assembly
Continue assembling the chimney sections up through the
ceiling firestops as needed. While doing so, be aware of the
height and unsupported chimney length limitations given un-
der Section 5.A. Chimney Requirements.
Check each section by pulling up slightly from the top to en-
sure proper engagement before installing the succeeding
sections. If they have been connected correctly, they will not
disengage when tested.
I. Secure the Chimney
When offsets and returns are joined to straight pipe sections,
they must be locked into position with the screws provided*
(outer only), using the predrilled holes. To prevent gravity
from pulling the chimney sections apart, the returns and the
chimney stabilizers have hanger straps for securing these
parts to joists or rafters. See Figure 24.3.
*
Use #6 or #8 sheet metal screw, or larger, no longer than
1/2 in. (13mm).
WARNING
Fire Risk
Secure offsets with screws (not to exceed
1/2 in. / 13mm in length).
Secure returns with strapping.
Straight chimney sections may be secured with screws
(not to exceed 1/2 in./13 mm in length) at the joints.
Keep chimney sections from separating or twisting.
Page 24
Heatilator • Constitution EPA Fireplace • 480-1091C
24 in.
(610mm)
Insulation
10-1/2 in.
(267mm)
Chimney
Figure 24.1 Install Attic Insulation Shield Above the Ceiling
14-1/2 in. (368 mm)
Insulation
24 in.
(610 mm)
10-1/2 in.
(267 mm)
Chimney
Figure 24.2 Install Attic Insulation Shield Below the Ceiling
Straps
Optional
Additional
Support
Figure 24.3 Secure the Chimney
Tabs
14-1/2 in. (368mm)
2 in. (51mm)
Attic Insulation
Shield
Ceiling Firestop
Tabs
Attic
Insulation
Shield
2 in. (51mm)
Ceiling Firestop
Ceiling
Firestop
Joint
Band
(Optional)
November 11, 2008