Carrier KGANP5201VSP Installation Instructions Manual page 17

Gas convection kit natural-to-propane for variable speed, condensing and non-condensing gas furnace
Table of Contents

Advertisement

1.Be sure m ain g as and electric supplies
to furnace
are off.
2. Remove
l/8-in.
(3 ram) pipe plug from manifold
pressure
tap on downstream
side of gas valve.
3. Attach
manometer
to manifold
pressure
tap on gas valve.
(see Fig. 28.)
4. Turn gas supply manual
shutoff valve to ON position.
5. Turn furnace gas valve switch
to ON position.
6. Check all threaded
pipe connections
for gas leaks.
7. Turn on furnace
power
supply.
GAS
INPUT
RATE
INFORMATION
The gas input rate for propane
is the same as for natural
gas. See
furnace
rating plate on blower
door for input rate. The input rate
for propane
is determined
by manifold
pressure
and orifice size.
The gas valve
must be set for Maxinmm
Heat first and then set
for Minimum
heat on Modulating
furnaces.
Furnace
gas input
rate on rating
plate is for installations
at altitudes
up to 2000 ft.
(610 M).
In the U.S.A.,
the input rating for altitudes
above 2000 ft. (610M)
nmst be reduced
by 2 percent
for each 1000 ft. (305 M) above sea
level.
In Canada,
the input
rating
nmst
be derated
by 5 percent
for
altitudes
of 2000
ft. (610 M) to 4500
ft. (1372
M) above
sea
level.
The
Conversion
Kit Rating
Plate
accounts
for
high
altitude
derate.
SET
GAS
INPUT
RATE
1. Verify SW1-2 on furnace
control is turned
"ON".
2. Jumper
R and W/W1
thermostat
connections
to call for
heat.
3. Check
manifold
orifices
for gas leaks when main burners
ignite.
4. Adjust
gas manifold
pressure.
Refer
to Conversion
Kit
Rating Plate 337704-206.
5. Remove
caps that conceal
adjustment
screws for gas valve
regulators.
See Fig. 28.
6. Adjust
low-heat
manifold
pressure
for propane
gas. See
Fig. 28.
7. Turn
low-heat
adjusting
screw counterclockwise
(out)
to
decrease
input rate or clockwise
(in) to increase
input rate.
NOTE:
When
correct
input
is obtained,
main
burner
flame
should be clear blue, almost transparent
(see Fig. 32).
8. Jumper
R, W/WI
and W2 on control
center
thermostat
connections.
This keeps furnace
locked in high-heat
oper-
ation.
9. Adjust high-heat
manifold
pressure
for propane
gas.
10. Turn high-heat
adjusting
screw counterclockwise
(out) to
decrease
input rate or clockwise
(in) to increase
input rate.
11. Replace
caps that conceal
gas valve
regulator
adjustment
screws.
NOTE:
When
correct
input
is obtained,
main
burner
flame
should be clear blue, almost transparent
(see Fig. 32).
Burner Flame
Burner
Fig. 32 - Burner
Flame
Al1461
12. Remove
jumper
across R, Wl,
and W2 after high-heat
ad-
justment
to terminate
call for heat.
13. Turn setup switch SWI-2
on furnace
control to OFF posi-
tion.
14. Turn furnace gas valve switch
to OFF position.
15. Turn off furnace
power
supply.
16. Remove
manometer
and re-install
manifold
pressure
tap
plug.
17. Turn furnace gas valve switch
to ON position.
18. Turn on furnace
power
supply.
19. Set room thermostat
to call for heat.
20. Check
pressure
tap plug for gas leaks when main burners
ignite.
21. Check for correct burner
flame.
22. Observe
unit operation
through
2 complete
heating
cycles.
23. See Sequence
of Operation
in furnace
Installation,
Start-
up, and Operating
Instructions.
24. Set room thermostat
to desired
temperature.
25. After making
the required
manifold
pressure
adjustments,
check
and adjust the furnace
temperature
rise per the fur-
nace installation
instructions.
CHECK
LOW
GAS
PRESSURE
SWITCH
The newly
installed
low gas pressure
switch
is a safety
device
used to guard against adverse
burner
operating
characteristics
that
can result from low gas supply
pressure.
Switch
opens at not less
than 6.5 in. W.C. and closes at not greater than 10.2 in. W.C.
This switch
also prevents
operation
when the propane
tank level
is low
which
can
result
in gas with
a high
concentration
of
impurities,
additives,
and residues
that have settled to the bottom
of the tank. Operation
under
these conditions
can cause
harm to
the heat exchanger
system.
This
normally
open
switch
closes
when
gas
is supplied
to
gas
valve
under
normal
operating
pressure.
The closed switch
completes
control
circuit.
Should
an
interruption
or reduction
in gas supply
occur, the gas pressure
at
switch
drops
below
low gas pressure
switch
setting,
and switch
opens.
Any
interruption
in control
circuit
(in which
low
gas
pressure
switch
is wired)
quickly
closes
gas valve
and stops gas
flow to burners.
When normal
gas pressure
is restored,
the system
must be electrically
reset to re-establish
normal
heating
operation.
Before
leaving
installation,
observe
unit
operation
through
2
complete
heating
cycles. During
this time, turn gas supply to gas
valve off just long enough
to completely
extinguish
burner
flame,
then instantly
restore
full gas supply.
To ensure
proper
low gas
pressure
switch
operation,
observe
that there is no gas supply
to
burners
until after hot surface igniter begins
glowing.
LABEL
APPLICATION
1. Fill in Conversion
Responsibility
Label 337704-205
and
apply
to Blower
Access
Door of furnace
as shown.
Date,
name, and address of organization
making
this conversion
are required.
2. Attach
Conversion
Rating
Plate Label
337704-206,
see
Fig. 23, to Outer Door of furnace.
3. Attach
Gas Control
Conversion
label 337704-202
to gas
valve. Do not use 337704-203,
which
is similar.
CHECKOUT
1. Observe
unit operation
through
2 complete
heating
cycles.
2. See Sequence
of Operation
operation
in furnace
Installa-
tion, Start-Up,
and Operating
Instructions.
3. Set room thermostat
to desired
temperature.
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents