Secutron MR-2300 series Installation & Operation Manual page 38

Led fire alarm control panel
Hide thumbs Also See for MR-2300 series:
Table of Contents

Advertisement

Indicators, Controls and Operations
Fire Drill LED
The amber Fire Drill Indicator illuminates steadily while Fire Drill is active.
Acknowledge LED
If the Panel is configured as a two-stage system, the Acknowledge Indicator flashes amber at the Fast Flash Rate
while the Auto General Alarm Timer is timing out. The Acknowledge Indicator steadily illuminates when the Alarm
Timer is cancelled by the activation of the Acknowledge or Signal Silence buttons. If the Auto General Alarm Timer
times out and puts the Panel into General Alarm, the Indicator turns off.
General Alarm LED
In two-stage operation only, the red General Alarm Indicator illuminates steadily when the General Alarm button is
pushed, a General Alarm Initiating Circuit is activated, or the Auto General Alarm Timer times out. Once the General
Alarm Indicator has been turned on it will stay active until the panel is reset.
Walk Test LED
The amber Walk Test Indicator illuminates steadily to indicate that the panel is in Walk Test Mode. If the Panel is left
in this mode for over an hour with no operator activity, the panel will return to normal and the Walk Test indicator will
turn OFF.
CPU Fail LED
The amber CPU Fail LED Indicator flashes at the Trouble Flash Rate to indicate a microprocessor failure on the
main board.
Auxiliary Disconnect LED
The amber Auxiliary Disconnect Indicator flashes at the Trouble Rate when the Auxiliary Disconnect button is
pressed. It turns OFF when the Auxiliary Disconnect button is pressed a second time. When ON flashing, the
Auxiliary Disconnect Indicator signifies that the Auxiliary Alarm Relay is disconnected. Depending on the
programming the auxiliary disconnect switch can also disconnect the common alarm and supervisory relay, see
Configuration section. When the Auxiliary Disconnect LED is flashing, the trouble buzzer will also sound.
Signal Silence LED
The Signal Silence indicator flashes amber, at the trouble rate, when indication Circuits are Silenced either by the
Signal Silence button, or by the Auto Signal Silence Timer. It is turned off when the Signals are re-sounded by a
subsequent Alarm.
Battery Trouble LED
The amber Battery Trouble Indicator flashes at the Trouble Rate when the Battery is either low (below 20.4 VDC) or
disconnected.
Ground Fault LED
The amber Ground Fault Indicator flashes at the Trouble Rate when the Ground Fault Detector detects a Ground
Fault on any field wiring. It turns off when the Ground Fault is cleared.
System Reset LED
This indicator is activated for a short time when the RESET key is pressed.