Air Filter — A suitable air filter must be installed
in the return air system. Air filter pressure drop
must not exceed 0.08 inches w.c.
Condensate Drain — Condensate is removed
from the unit through the 3/4" female pipe fitting
located on the front side of the unit. (See Figure
4.) Install a 2 inch condensate trap in the drain
line of the same size and prime with water.
When connecting rigid drain line, hold the female
fitting with a wrench to prevent twisting. Do not
Condensate Drain
Figure 4. Condensate Drain
6
0"
Figure 3. Minimum Clearances
over-tighten! Refer to local codes and
restrictions for proper condensate disposal
requirements.

UNIT INSTALLATION

Ground Level — When installing the unit at
ground level, provide a concrete mounting
pad separate from the building foundation.
The pad must be level to insure proper
condensate disposal and strong enough to
support the unit's weight. Refer to Figure 2 .
Make sure the slab is a minimum of 2" above
the grade and in an area that drains well.
(Figure 5)
To avoid the risk of property damage
or personal injury; it is the rigger's
responsibility to insure that whatever
means are used to hoist the unit are
safe and adequate.
72"
36"