Circulating Air Supply; Air Ducts; Unconditioned Spaces; Acoustical Duct Work - Nordyne R8HE Series Installation Instructions Manual

Single package gas heating / electric cooling 3-phase & single phase (revision a)
Hide thumbs Also See for R8HE Series:
Table of Contents

Advertisement

CIRCULATING AIR SUPPLY

WARNING:
Products of combustion must not be allowed to
enter the return air ductwork or the circulating air
supply.Failure to prevent products of combustion
from being circulated into the living space can
create potentially hazardous conditions including
carbon monoxide poisoning that could result in
personal injury or death.
All return ductwork must be adequately sealed,
all joints must be taped, and the ductwork must
be secured to the unit with sheet metal screws.
When return air is provided through the bottom
of the unit, the joint between the unit and the
return air plenum must be air tight.
The roof curb or cement pad that the unit is
mounted must provide sound physical support of
the unit with no gaps,cracks,or sagging bewteen
the unit and pad.
Return air and circulating air ductwork must not
be connected to any other heat producing device
such as a fireplace insert, stove, etc. Doing so
may result in fire, explosion, carbon monoxide
poisoning, personal injury, or property damage.

Air Ducts

This unit is designed only for use with a supply and return
duct. Air ducts should be installed in accordance with the
standards of the National Fire Protection Association
"Standard for Installation of Air Conditioning Systems"
(NFPA 90A), "Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems" (NFPA
90B), and all applicable local codes. NFPA publications
are available by writing to: National Fire Protection
Association, Batterymarch Park, Quincy, ME 02269 or
visit www.NFPA.org on the web.
• Design the duct work according to Manual D by the Air
Conditioning Contractors of America (ACCA).
• The ducts must be properly sized not to exceed the
units maximum ESP rating at 400 SCFM per nominal
ton of cooling capacity.
• Duct work should be attached directly to the unit flanges
for horizontal applications.
• If a roof curb is installed, the ducts must be attached to
the curb hangers, not the unit.
• It is recommended that the outlet duct be provided
with a removable access panel. The opening should
be accessible when the unit is installed in service and
shall be sizes so that smoke or reflected light may be
observed inside the casing to indicate the presence of
leaks in the heat exchanger. The cover for the opening
shall be attached in a way that will prevent leaks.
• If outside air is utilized as return air to the unit for
ventilation or to improve indoor air quality, the system
must be designed so that the return air to the unit is not
less than 50° F (10° C) during heating operation.
• If a combination of indoor and outdoor air is used, the
ducts and damper system must be designed so that the
return air supply to the furnace is equal to the return air
supply under normal, indoor return air applications.

Unconditioned Spaces

All duct work passing through unconditioned space must
be properly insulated to minimize duct losses and prevent
condensation. Use insulation with an outer vapor barrier.
Refer to local codes for insulation material requirements.

Acoustical Duct Work

Certain installations may require the use of acoustical
lining inside the supply duct work.
• Acoustical insulation must be in accordance with the
current revision of the Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) application
standard for duct liners.
• Duct lining must be UL classified batts or blankets with
a fire hazard classification of FHC-25/50 or less.
• Fiber duct work may be used in place of internal duct
liners if the fiber duct work is in accordance with the
current revision of the SMACNA construction standard
on fibrous glass ducts. Fibrous duct work and internal
acoustical lining must be NFPA Class 1 air ducts when
tested per UL Standard 181 for Class 1 ducts.

UNIT INSTALLATION

Packaging Removal

Remove the shipping carton and User's Manual from the
equipment. Set aside the 13" x 2" PVC pipe for later use
when installing the heat exchanger condensate drain and
vent kit. Take care not to damage the coil or cabinet when
removing the carton. For rooftop installations, remove
and discard the two supports attached beneath the unit
Rigging & Hoisting
WARNING:
To avoid the risk of property damage, personal
injury, or death, it is the rigger's responsibility
to ensure that whatever means are used to hoist
the unit are safe and adequate:
• The lifting equipment must be adequate for the
load. Refer to
Table 7 (page 27)
• The unit must be lifted from the holes in the
base rails using cables or chains.
• Spreader bars are required to protect the unit
and ensure even loading.
• Keep the unit in an upright position at all times.
The rigging must be located outside the units
center of gravity. Refer to
for locating the center of gravity.
• All panels must be securely in place during
rigging and hoisting, except control access
panel. See
page 48
setting of unit requirements.
for unit weights.
Figure 7 (page 20)
for additional lifting and
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ppg3he seriesR8he-a

Table of Contents