8-15 kva
Hide thumbs Also See for 9155:
Table of Contents

Advertisement

Table 20. Model Specifications (continued)
Output Voltage (line–line)
Output Voltage (line–neutral)
Input Current*
Output Current
Output kVA (line–line loads)
Output kVA (line–neutral loads)
Output kW
Output Peak Current
Efficiency (minimum)
Power Dissipation (BTU/hr)
DC Voltage (supply)
Output Voltage (line–line)
Output Voltage (line–neutral)
Input Current*
Output Current
Output kVA (line–line loads)
Output kVA (line–neutral loads)
Output kW
Output Peak Current
Efficiency (minimum)
Power Dissipation (BTU/hr)
DC Voltage (supply)
*Input current for the input isolation transformer is 4% higher than for the UPS.
Powerware
9155 UPS (8–15 kVA) User's Guide
®
200
220
100
110
57A
52A
50A
45A
10.0
10.0
10.0
10.0
9.0
9.0
110
110
87%
87%
4175
4175
192
192
200
220
100
110
46A
42A
40A
36A
8.0
8.0
8.0
8.0
7.2
7.2
88
88
87%
87%
3300
3300
192
192
164201553 Rev D www.powerware.com
S
Model 10 kVA
240
208
120
120
48A
48A
42A
42A
10.0
8.7
10.0
10.0
9.0
9.0
110
110
87%
87%
4175
4175
192
192
Model 8 kVA
240
208
120
120
38A
38A
33A
33A
8.0
6.9
8.0
8.0
7.2
7.2
88
88
87%
87%
3300
3300
192
192
Specifications
220
127
45A
39A
8.7
10.0
9.0
110
87%
4175
192
220
127
36A
31A
6.9
8.0
7.2
88
87%
3300
192
89