Configuring the UPS for EBMs

Powerware
9155 UPS (8–15 kVA) User's Guide
®
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1. Press any button on the front panel display to activate the menu
options.
2. Using the button, scroll to the Settings menu.
3. Press the
4. Using the button, scroll to the Number of Battery Strings
option and press the
5. Use the or arrow buttons to select the number of strings
according to your UPS configuration:
All 2-High UPS and EBM Cabinets*
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
UPS + 4 EBMs
All 3-High UPS and EBM Cabinets*
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.
UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.
6. Press the
7. Press the
ESC
164201553 Rev D www.powerware.com
S
button twice to select the User Settings menu.
button.
button to save the setting.
button until the Eaton Powerware logo appears.
Operation
Number of Strings
6
10
14
18
Number of Strings
10
16
22
75