UPS Maintenance

Using the Wall-Mounted Bypass Switch

Table 15. Wall-Mounted Bypass Switch Positions
Switch Position
UPS
Connects the UPS output to the load.
LINE
Connects the load directly to AC input power and disconnects UPS output. AC input
power is still connected to the UPS input.
SERVICE
Like the LINE position, SERVICE connects the load directly to AC input power and
disconnects UPS output.
from the UPS, this is the appropriate position for UPS maintenance or repair.
OFF
Disconnects the load from the UPS output power and AC input power, as well as AC
input power to the UPS input.
82
Powerware
The wall-mounted bypass switch is rated at 80A/300 Vac and has four
positions as described in Table 15.
NOTE
In the UPS or LINE position, AC input power is still connected to
the input terminals inside the UPS.
However, because SERVICE also disconnects AC input
You must press the red button beside the switch before turning the
Maintenance Bypass switch.
Figure 43. Wall-Mounted Maintenance Bypass Switch
9155 UPS (8–15 kVA) User's Guide
®
Description
164201553 Rev D www.powerware.com