1.2.3 Storage

Store the UPS in a dry location, storage temperature must be within –20°C to +45°C.
If the unit is stored for a period exceeding 3 months, the batteries must be recharged
periodically.
Connect the unit to the mains and switch it on for a period of approx. 48 hours, minimum
every 3 months.

1.2.4 Batteries

• When replacing the batteries, use the same number and voltage (V) / capacity (Ah).
• Proper disposal or recycling of the batteries is required.
Refer to your local codes for disposal requirements.
• Never dispose of batteries in a fire: they may explode.
• Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
• Avoid charging in a sealed container.
• Never short circuit batteries. When working with batteries, remove watches, rings or other
metal objects, and only use insulated tools.
OPM_LPS_31E_8K0_20K_1GB_V010.doc
7/40