12
Chapter 2 Mechanical Installation
4. Be careful not to damage the waterproof layer and observe the local rules and regulations when the condenser is
installed on the roof of building.
5. Position the condenser higher than the indoor unit to ensure normal oil return.
6. Follow the installation arrows on the condenser for the installation direction.
2.5.2 Space Requirements
Note
1. A 4000mm clearance is required around the condenser air outlet.
2. The 600mm service spaces are required on the four sides of the condenser.
The condenser needs sufficient installation and service space around the installation place. The detailed space
requirements are shown in Figure 2-15 and Figure 2-16.
2.5.3 Mounting base dimension
Mounting base for horizontal installation
The mounting base for horizontal installation is shown in Figure 2-17 and the mounting base dimensions of each
model are listed in Table 2-3.
Air flow
Figure 2-15 Horizontal installation space requirement (unit: mm)
Figure 2-16 Vertical installation space requirement (unit: mm)
DM Series 16kW Air Conditioner User Manual
Air flow
1200
4000
Air flow
600
600