Chapter 2 Installation
Unpacking
Remove the paper package and foam of the condenser but reserve the protection cardboard of fins. The protection
cardboard of fins and the cushion pad of U tube on the end of the condenser should be removed after the condenser is
in its installation position.
Note
1. If the condenser is to be placed horizontally, you should complete the installation of legs while the condenser is located
vertically.
2. When moving the condenser by hand, to avoid distortion and system leakage, do not touch the copper pipes.
Inspection
After receiving the product, you should check the accessories against the packing list. If any parts are found missing or
damaged, please report to the carrier immediately. If any covert damage is found, please report to the carrier and the
distributor too.

2.2 Installation Notes

The installation notes of the condenser are as follows:
1. To ensure the heat dissipation capacity, install the condenser in the place with smooth air flow. Do not install it
where the coil of the condenser may be obstructed by dust and snow. Ensure that there is no steam or waste heat
around.
2. If possible, the horizontal installation is recommended to reduce the noise.
3. The condenser should be installed as far away as possible from residential areas (≥15m).
4. Be careful not to damage the waterproof layer and observe the local rules and regulations when the condenser is
installed on the roof of building.
5. Position the condenser higher than the indoor unit to ensure normal oil return.
6. Follow the installation arrows on the condenser for the installation direction.

2.3 Space Requirements

Note
1. A 4000mm clearance is required around the condenser air outlet.
2. The 600mm service spaces are required on the four sides of the condenser.
The condenser needs sufficient installation and service space around the installation place. The detailed space
requirements are shown in Figure 2-3 and Figure 2-4.
Air flow
Figure 2-3 Horizontal installation space requirement (unit: mm)
Liebert PEX Condenser User Manual
Air flow
1200
600