Rotation Pulse Check On The Outdoor Unit Pcb - Daikin FTXN09KEVJU Service Manual

Inverter pair wall mounted type k-series
Hide thumbs Also See for FTXN09KEVJU:
Table of Contents

Advertisement

Check
5.8

Rotation Pulse Check on the Outdoor Unit PCB

Check No.16
09/12 class
1. Check that the voltage between the pins 10 - 11 is 15 VDC.
2. Check if the Hall IC generates the rotation pulse (0 ~ 15 VDC) 4 times between the pins 10 -12,
15/18/24 class
Make sure that the voltage of 320 ± 30 V is applied.
1. Set operation off and power off. Disconnect the connector S70.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 15 VDC.
5. Keep operation off and power off. Connect the connector S70.
6. Check whether 2 pulses (0 ~ 15 VDC) are output at the pins 1 - 4 when the fan motor is rotated
When the fuse is melted, check the outdoor fan motor for proper function.
122
10 - 13, when the fan motor is manually rotated once.
13
12
11
10
1 turn by hand.
If NG in step 2  Defective PCB Replace the outdoor unit PCB.
If NG in step 4  Defective Hall IC Replace the outdoor fan motor.
If OK in both steps 2 and 4  Replace the outdoor unit PCB.
PCB
S70
1
2
3
4
5
6
7
S70
HV (Hall IC)
HU (Hall IC)
15 VDC
Free pin
9
Free pin
8
Phase W
7
Free pin
6
Free pin
5
Phase V
4
Free pin
3
Free pin
2
Phase U
1
Actual rotation pulse output (0 ~ 15VDC)
Rotation command pulse input (0 ~ 15VDC)
15 VDC
320 VDC
SiUS041111
(R11907)
(R10811)
Service Diagnosis