Thermistor Or Related Abnormality (Outdoor Unit) - Daikin FTXN09KEVJU Service Manual

Inverter pair wall mounted type k-series
Hide thumbs Also See for FTXN09KEVJU:
Table of Contents

Advertisement

Troubleshooting

4.19 Thermistor or Related Abnormality (Outdoor Unit)

H9, J3, J6, P4
Remote
Controller
Display
Method of
This fault is identified based on the thermistor input voltage to the microcomputer.
Malfunction
A thermistor fault is identified based on the temperature sensed by each thermistor.
Detection
 The thermistor input voltage is above 4.96 V or below 0.04 V with the power on.
Malfunction
 J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
Decision
Conditions
 Disconnection of the connector for the thermistor
Supposed
 Defective thermistor corresponding to the error code
Causes
 Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger thermistor
 Defective outdoor unit PCB
Troubleshooting
In case of "P4"
Replace the outdoor unit PCB.
P4 : Radiation fin thermistor
104
temperature.
in cooling operation, or indoor heat exchanger thermistor in heating operation)
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
SiUS041111
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents