Troubleshooting
4.14 Discharge Pipe Temperature Control
F3
Remote
Controller
Display
Method of
An error is determined with the temperature detected by the discharge pipe thermistor.
Malfunction
Detection
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
Malfunction
Decision
The error is cleared when the discharge pipe temperature has dropped below B.
Conditions
09/12 class
Stop temperatures
(1) above 50 Hz (rising), above 45 Hz (dropping)
(2) 39 ~ 50 Hz (rising), 34 ~ 45 Hz (dropping)
(3) below 39 Hz (rising), below 34 Hz (dropping)
15/18/24 class
Stop temperatures
(1) above 50 Hz (rising), above 45 Hz (dropping)
(2) 35 ~ 50 Hz (rising), 30 ~ 45 Hz (dropping)
(3) below 35 Hz (rising), below 30 Hz (dropping)
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
Supposed
Causes
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four-way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
96
stops.
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
A
°C
°F
110
230
105
221
100
212
A
°C
°F
118
244.4
110
230
93
199.4
SiUS041111
B
°C
°F
97
206.6
92
197.6
87
188.6
B
°C
°F
85
185
77
170.6
60
140
Service Diagnosis